Plan Review Notes For Permit 01091712 |
Permit Number |
01091712 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-10-30 00:00:00 | ********************DENIED************** | | | | PLANS DO NOT SPECIFY THAT DUCTWORK IS | | IN A FIRE RATED ENCLOSURE. | | | | AS PER 1997 SMC 610.4, DUCTS PENETRATING | | ONLY ONE FLOOR MAY BE PROTECTED BY | | INSTALLING A LISTED FIRE DAMPER WHERE | | THE FLOOR IS PIERCED IN LIEU OF AN | | ENCLOSURE. | | | | OUTSIDE AIR CALCULATIONS ONLY INDICATE | | OFFICE AREAS AND STORAGE AREAS.THERE | | IS NO "STORAGE AREA" INDICATED ON THE | | FLOOR PLAN.ONLY 2 PRIVATE OFFICES, A | | WORKROOM AND CONSULATION.PLEASE | | REVISE OUTSIDE AIR CALCULATIONS TO | | REFLECT ALL AREAS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|