Plan Review Notes
Plan Review Notes For Permit 01091712
Permit Number 01091712
Review Stop M
Sequence Number 1
Notes
Date Text
2001-10-30 00:00:00********************DENIED**************
  
 PLANS DO NOT SPECIFY THAT DUCTWORK IS
 IN A FIRE RATED ENCLOSURE.
  
 AS PER 1997 SMC 610.4, DUCTS PENETRATING
 ONLY ONE FLOOR MAY BE PROTECTED BY
 INSTALLING A LISTED FIRE DAMPER WHERE
 THE FLOOR IS PIERCED IN LIEU OF AN
 ENCLOSURE.
  
 OUTSIDE AIR CALCULATIONS ONLY INDICATE
 OFFICE AREAS AND STORAGE AREAS.THERE
 IS NO "STORAGE AREA" INDICATED ON THE
 FLOOR PLAN.ONLY 2 PRIVATE OFFICES, A
 WORKROOM AND CONSULATION.PLEASE
 REVISE OUTSIDE AIR CALCULATIONS TO
 REFLECT ALL AREAS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.