Plan Review Notes
Plan Review Notes For Permit 01091712
Permit Number 01091712
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-10-31 00:00:001) A SINGLE MEANS OF EGRESS IS SHOWN
 FROM THE SECOND WHICH IS NOT
 PROTECTED. THE FIRE CODE REQUIRES
 AT LEAST TWO MEANS OF EGRESS SHALL BE
 PROVIDED AT EVERY LEVEL. THE TWO
 EXCEPTIONS ARE AS FOLLOWS:
  
 # 1, OCCUPANT LOAD OF LESS THAN 100
 PERSONS, DIRECT ACCESS TO THE OUTSIDE,
 TOTAL TRAVEL DISTANCE LESS THAN 100
 FEET, AND COMPLETELY SEPARATED FROM
 OTHER PARTS OF THE BUILDING.
  
 # 2, BUILDING LESS THAN THREE STORIES,
 OCCUPANT LOAD LESS THAN 30 PERSONS,
 TRAVEL DISTANCE LESS THAN 100 FEET, AND
 EXIT IS ENCLOSED.
  
 UNPROTECTED VERTICAL OPENINGS ARE
 PERMITTED WITH THE FOLLOWING CONDITIONS:
 THE AREA IS LOW HAZARD OR ORDINARY
 HAZARD, THE LOWEST OR NEXT LEVEL IS
 THE STREET FLOOR, AREA IS OPEN AND
 UNOBSTRUCTED, AND EXIT CAPACITY CAN
 PROVIDE FOR ALL OCCUPANTS. THE OTHER
 EXCEPTION INDICATES CONNECTION WITH
 TWO FLOORS, THE OPENING IS NOT A
 REQUIRED MEANS OF EGRESS, OPENING IS
 NOT CONNECTED WITH STAIRWAYS OR
 CORRIDORS, AND A FIRE SPRINKLER SYSTEM
 IS PROVIDED.
  
 BUISNESS OCCUPANCIES ACCORDING TO THE
 FIRE CODE IS CONSIDERED AN ORDINARY
 HAZARD. (CONTENTS)
  
 THE CODE ALSO INDICATES THAT WHERE
 CHAPTERS 1-7 ARE DIFFERENT FROM 8-30,
 THE INFORMATION IN CHAPTERS 8-30
 SHALL APPLY.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910