Plan Review Notes
Plan Review Notes For Permit 01091712
Permit Number 01091712
Review Stop E
Sequence Number 1
Notes
Date Text
2001-10-30 00:00:00******************* UNSAT ************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 SUBMITTED FOR PANELS BUT NOT FOR MAIN.
  
 2)NOTE: PLEASE NOTE THAT THE PLANS DO
 NOT SHOW ANY LOAD CALCULATIONS? ALSO
 ALL CONTINOUS LOADS ARE TO BE SHOWN AT
 125% . 215-5/215-2-3/ 230-42 ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372