2001-12-21 00:00:00 | APPROVED WITH PROVISO: |
| 1-FLOOD ZONE AO. NEED THE ELEVATION |
| CERTIFICATE. |
| 2-NEED ADDITIONAL SOIL BORINGS FOR EACH |
| STRUCTURE AS RECOMMENDED ON THE PRE- |
| LIMINARY SOIL TEST REPORT. |
| 3-PRODUCT APPROVAL FOR SINGLE HUNG |
| WINDOWS EXPIRED. |
| -PROVIDE PRODUCT APPROVAL FOR FRENCH |
| DOOR WITH SIDELITES IF OPTION SELECTED |
| 4-MASTER BEDROOM CAN'T HAVE OPTION OF |
| DOORS AT REAR ELEVATION BECAUSE IT |
| WILL NOT COMPLY WITH TABLE 600 SBC/97. |
| ONLY SIDE DOOR OPTION WILL COMPLY. |
| 5-PROVIDE COMPLETE INFORMATION FOR STORM |
| PANELS UNDER A SEPARATE PERMIT. |
| 6-TRUSS DRAWINGS: |
| -UPDATE ALL GENERAL TRUSS DETAILS. USE |
| ASCE 7-95 FOR 140MPH, NOT ASCE 7-93. |
| SEE COMMENTS ON TRUSSES. |
| -DESIGNER OF RECORD TO REVIEW ALL TRUSS |
| DRAWINGS AND CLEARLY INDICATE WHO |
| REVIEW THE TRUSSES. (NAME OF FIRM). |
| 7-PROVIDE MANUFACTURER'S CERTIFICATION |
| FOR 2 HR FIRE RATED CONCRETE BLOCK |
| ACCORDING TO THE EQUIVALENT THICKNESS |
| AND AGGREGATES USED. SEE SECTION 709.3 |
| SBC 1997. |
| |
| NOTES: |
| -DRAWINGS AND COMMENTS TO BE FILED UNDER |
| PERMIT #01091691. |
| -THESE COMMENTS APPLY TO PERMIT #S: |
| 01091691, 01091695, 01091697, 01091699 |
| 01091701 AND 01091706. |