Plan Review Notes
Plan Review Notes For Permit 01091542
Permit Number 01091542
Review Stop P
Sequence Number 2
Notes
Date Text
2003-04-29 00:00:00DENIED
 REFERENCE:SPC-94
  
 1) CHANGES TO A SIGNED AND SEALED SET
 OF PLANS SHALL BE SIGNED AND SEALED BY
 ARCHITECT OR ENGINEER OF RECORD.
 2) PER NEC-99SECTION 422.17 - EACH
 ELECTRICALLY HEATED APPLIANCE THAT IS
 INTENDED BY SIZE, WEIGHT, AND SERVICE TO
 BE IN A FIXED POSITION SHALL BE PLACED
 SO AS TO PROVIDE AMPLE PROTECTION BE-
 TWEEN THE APPLIANCE AND ADJACENT COMBUST
 IBLE MATERIAL.
 3) PLEASE PROVIDE MANUF. INFO. FOR STEAM
 UNIT. UNIT SHALL BE LISTED BY A RECOG-
 NIZED TESTING ORGANIZATION .
 4) ELECTRICAL REVISION REQUIRED ALSO.
 6) PLEASE INDICATE WHERE THE BACKFLUSH
 LINE WILL BE DRAINING TO.
 7) PLEASE INDICATE WHERE THE P/T RELEIF
 VALVE WILL DRAIN TO.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692