Plan Review Notes For Permit 01091542 |
Permit Number |
01091542 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-04-29 00:00:00 | DENIED | | REFERENCE:SPC-94 | | | | 1) CHANGES TO A SIGNED AND SEALED SET | | OF PLANS SHALL BE SIGNED AND SEALED BY | | ARCHITECT OR ENGINEER OF RECORD. | | 2) PER NEC-99SECTION 422.17 - EACH | | ELECTRICALLY HEATED APPLIANCE THAT IS | | INTENDED BY SIZE, WEIGHT, AND SERVICE TO | | BE IN A FIXED POSITION SHALL BE PLACED | | SO AS TO PROVIDE AMPLE PROTECTION BE- | | TWEEN THE APPLIANCE AND ADJACENT COMBUST | | IBLE MATERIAL. | | 3) PLEASE PROVIDE MANUF. INFO. FOR STEAM | | UNIT. UNIT SHALL BE LISTED BY A RECOG- | | NIZED TESTING ORGANIZATION . | | 4) ELECTRICAL REVISION REQUIRED ALSO. | | 6) PLEASE INDICATE WHERE THE BACKFLUSH | | LINE WILL BE DRAINING TO. | | 7) PLEASE INDICATE WHERE THE P/T RELEIF | | VALVE WILL DRAIN TO. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 | | (561) 805-6721 | | FAX (561) 653-2692 |
|