Plan Review Notes For Permit 01091474
Permit Number 01091474
Review Stop ENG
Sequence Number 1
Notes
Date Text
2001-10-18 00:00:00FAILED:
 1. CONSTRUCTION OF GAZEBO MUST CLEAR THE
 40.88' UE ON EAST SIDE.
 2. PLEASE SUBMIT STORM WATER CALCULATION
 FOR OUR REVIEW AND APPROVAL IF NOT
 SUBMITTED TO JOSE DEL RIO,IF SUBMITTED
 , THEN STATE THE STATUS.
 3. PLEASE SUBMIT PERVIOUS AND IMPERVIOUS
 AREA CALCULATIONS FOR ENTIRE SITE,
 SIGNED & SEALED.
 4. STORM DRAIN #6 SHOWS I.E = 12.5(N),
 IT SHOULD SHOW 1.E = 12.5(W)
 5. PROVIDE 4" CONCRETE FLUME AROUND
 THE EXISTING CATCH BASIN GRATE IN THE
 PROPOSED SWALE AREA.
 6. PLEASE SHOW DRAINAGE FOR THE POOL.
 7. LIGHT POLE RELOCATIONS MUST BE
 COORDINATED WITH PUBLIC UTILITIES.
 8. ANY WORK WITHIN PUBLIC R.O.W WILL
 REQIURES A SEPATRATE PERMIT FROM CITY
 ENGINEER'S OFFICE, 659-8040.
 9. NEW CONNECTIONS TO CITY SERVICES
 AND INSTALLATION OF BACKFLOW PREVENTERS
 WOULD REQUIRE PERMIT AND APPROVAL FROM
 PUBLIC UTILITIES, 659-8040.
 10. BEGIN TYPE "F" CURB AT THE EDGE OF
 20' FIRE ACCESS LANE WITH ADEQUATE
 TRANSITIONS AS MARKED ON SHEET C-4.
 11. EXCAVATIONS TO ELEV. 15' IN
 RETENSION AREA WOULD LEAVE +/- 1' OF
 COVER FOR THE EXISTING 36" WATER MAIN
 (PRESSURE PIPE), PLEASE VERIFY.
  
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI