Plan Review Notes
Plan Review Notes For Permit 01091471
Permit Number 01091471
Review Stop M
Sequence Number 8
Notes
Date Text
2003-03-06 00:00:00DENIED:MECHANICAL PERMIT 02041735
  
 1.DUCT PENETRATING "FIRE ROOM" HAS
 CHANGED TO FLEX.THIS IS A ONE HOUR
 PARTITION WALL, AS PER 1997 SMC 610.1.3
 EXCEPTIONS FOR LOCATION OF FIRE DAMPERS
 SHALL COMPLY WITH #3 ITEMS 1 THRU 4.
  
 1. DUCT SHALL NOT EXCEED 100 SQ IN
 2. DUCT SHALL BE OF .0217" MIN STEEL.
 3. DUCT SHALL CONTINUE W/NO OPENINGS
 FOR NOT LESS THAN 5' FROM RATED
 WALL.
 4. DUCT SHALL BE INSTALLED ABOVE A
 CEILING.
 PLEASE NOTE DUCT COMPLIES WITH ITEMS 1
 AND 4.
  
 2.CLARIFY DUCT PENETRATION THROUGH
 BATHROOM1 HR PATITION WALL.NO FIRE
 INDICATED ON PLAN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.