Plan Review Notes For Permit 01091471 |
Permit Number |
01091471 |
|
Review Stop |
M |
Sequence Number |
8 |
|
Notes |
Date |
Text |
2003-03-06 00:00:00 | DENIED:MECHANICAL PERMIT 02041735 | | | | 1.DUCT PENETRATING "FIRE ROOM" HAS | | CHANGED TO FLEX.THIS IS A ONE HOUR | | PARTITION WALL, AS PER 1997 SMC 610.1.3 | | EXCEPTIONS FOR LOCATION OF FIRE DAMPERS | | SHALL COMPLY WITH #3 ITEMS 1 THRU 4. | | | | 1. DUCT SHALL NOT EXCEED 100 SQ IN | | 2. DUCT SHALL BE OF .0217" MIN STEEL. | | 3. DUCT SHALL CONTINUE W/NO OPENINGS | | FOR NOT LESS THAN 5' FROM RATED | | WALL. | | 4. DUCT SHALL BE INSTALLED ABOVE A | | CEILING. | | PLEASE NOTE DUCT COMPLIES WITH ITEMS 1 | | AND 4. | | | | 2.CLARIFY DUCT PENETRATION THROUGH | | BATHROOM1 HR PATITION WALL.NO FIRE | | INDICATED ON PLAN. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|