Plan Review Notes For Permit 01091471 |
Permit Number |
01091471 |
|
Review Stop |
FIRE |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2002-09-26 00:00:00 | THE REQUIRED FIRE PUMP WILL BE REQUIRED | | TO PROVIDE AT LEAST 750 GPM AT THE | | ROOF AT 65 PSI RESIDUAL PRESSURE AT THE | | SAME LOCATION. THE FIRE PUMP AND | | APPURTENANT EQUIPMENT ARE TO BE | | INSTALLED IN ACCORDANCE WITH NFPA 20. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|