Plan Review Notes
Plan Review Notes For Permit 01091471
Permit Number 01091471
Review Stop E
Sequence Number 4
Notes
Date Text
2002-07-25 00:00:00************* UNSAT ******************
 ***** GENERATORS SPEC NAD CALCULATIONS**
  
 1)NOTE: PLEASE NOTE THAT GENERATOR SPECS
 AND CALCS THAT ARE SUBMITTED FOR RECORD
 MUST BE SIGNED,DATED AND SEALED BY THE
 ENGINEER OF RECORD. 471.025
 MUST BE ORIGINAL.
  
 2)NOTE: PLEASE NOTE THAT SHEETS DO NOT
 CORRELATE? ONE SHOWS CALCS AT 120/208
 AND GENERATOR AT 277/480V??
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372