Plan Review Notes For Permit 01091471 |
Permit Number |
01091471 |
|
Review Stop |
B |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2002-07-11 00:00:00 | THE SEVERAL AND VARIOUS METRO DADE | | NOTICE OF ACCEPTANCES FOR THE DOORS AND | | WINDOWS SUBMITTED AS SHOPDRAWINGS ON | | 6/25/02 ARE REQUIRED TO HAVE A SEPARATE | | PERMIT APPLICATION, SINCE THEY WERE NOT | | INCLUDED WITH THE ORIGIANL PERMIT PLANS. | | | | | | PLEASE INCLUDE A SKETCH INDICATING THE | | LOCATION OF THE WINDOW OR DOOR TO BE | | INSTALLED.SHOW THE DESIGN PRESSURES | | FOR THE OPENINGS ON THE SKETCH.ENSURE | | THAT THE PRESSURES ON THE NOA'S AGREE | | WITH THE BUILDING DESIGN AND IN CASES | | WHERE THERE IS MORE THAN ONE METHOD OR | | UNIT ON THENOA THAT THE INTENDED METHOD | | OR UNIT IS CLEARLY SELECTED AND MARKED | | ON THE NOA. | | | | SOME OF THE NOA'S INDICATED THE | | REQUIREMENT FOR "HURRICANE PROTECTION" | | IE SHUTTERS.THE BUILDING OFFICIAL'S | | INTERPRETATION OF THE CODE IS THAT | | SHUTTERS ARE NOT TO BE SUBSTITUTED FOR | | IMPACT RESISTANT GLAZING IN LARGE | | BUILDINGS AND/OR LARGE NUMBERS OF | | OPENINGS.SEE THE ATTACHED | | IMPLEMENTATION STANDARD. |
|