Plan Review Notes
Plan Review Notes For Permit 01091471
Permit Number 01091471
Review Stop B
Sequence Number 4
Notes
Date Text
2002-07-11 00:00:00THE SEVERAL AND VARIOUS METRO DADE
 NOTICE OF ACCEPTANCES FOR THE DOORS AND
 WINDOWS SUBMITTED AS SHOPDRAWINGS ON
 6/25/02 ARE REQUIRED TO HAVE A SEPARATE
 PERMIT APPLICATION, SINCE THEY WERE NOT
 INCLUDED WITH THE ORIGIANL PERMIT PLANS.
  
  
 PLEASE INCLUDE A SKETCH INDICATING THE
 LOCATION OF THE WINDOW OR DOOR TO BE
 INSTALLED.SHOW THE DESIGN PRESSURES
 FOR THE OPENINGS ON THE SKETCH.ENSURE
 THAT THE PRESSURES ON THE NOA'S AGREE
 WITH THE BUILDING DESIGN AND IN CASES
 WHERE THERE IS MORE THAN ONE METHOD OR
 UNIT ON THENOA THAT THE INTENDED METHOD
 OR UNIT IS CLEARLY SELECTED AND MARKED
 ON THE NOA.
  
 SOME OF THE NOA'S INDICATED THE
 REQUIREMENT FOR "HURRICANE PROTECTION"
 IE SHUTTERS.THE BUILDING OFFICIAL'S
 INTERPRETATION OF THE CODE IS THAT
 SHUTTERS ARE NOT TO BE SUBSTITUTED FOR
 IMPACT RESISTANT GLAZING IN LARGE
 BUILDINGS AND/OR LARGE NUMBERS OF
 OPENINGS.SEE THE ATTACHED
 IMPLEMENTATION STANDARD.