Plan Review Notes For Permit 01091471 |
Permit Number |
01091471 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2002-04-10 00:00:00 | PROVISO: | | | | THE REVISED SUSPENDED CEILING DETAIL ON | | SHEET A-11.1 LACKS SPECIFIC CONSTRUCTION | | INFORMATION.PROVIDE A SKETCH | | DETAILING SPACING OF FRAMING CHANNELS, | | TYPE AND NUMBER OF FASTENERS AND THE | | GAUGE OF THE FRAMING MEMBERS. | | STATEMENTS SUCH AS "ANCHOR TO STRUCTURE | | ABOVE" ARE NOT ADEQUATE.PLEASE SUBMIT | | THIS INFORMATION BEFORE CONSTRUCTION. | | | | THE USE OF HURRICANE PANELS IS SUBJECT | | TO THE BUILDING OFFICIAL'S | | INTERPRETATION PAPER.SEE ATTACHED. | | | | THE DRAWINGS NOTED IN THE METRO DADE | | REPORTS NUMBERED 00-0628.11, 01-0629.08 | | AND99-0218.01 ARE MISSING.ALSO, | | PROVIDE ABLDG SKETCH OR TABLE DEPICTING | | THE PRESSURES FOR THE COMPONENTS AND | | CLADDING. |
|