Plan Review Notes
Plan Review Notes For Permit 01091471
Permit Number 01091471
Review Stop B
Sequence Number 3
Notes
Date Text
2002-04-10 00:00:00PROVISO:
  
 THE REVISED SUSPENDED CEILING DETAIL ON
 SHEET A-11.1 LACKS SPECIFIC CONSTRUCTION
 INFORMATION.PROVIDE A SKETCH
 DETAILING SPACING OF FRAMING CHANNELS,
 TYPE AND NUMBER OF FASTENERS AND THE
 GAUGE OF THE FRAMING MEMBERS.
 STATEMENTS SUCH AS "ANCHOR TO STRUCTURE
 ABOVE" ARE NOT ADEQUATE.PLEASE SUBMIT
 THIS INFORMATION BEFORE CONSTRUCTION.
  
 THE USE OF HURRICANE PANELS IS SUBJECT
 TO THE BUILDING OFFICIAL'S
 INTERPRETATION PAPER.SEE ATTACHED.
  
 THE DRAWINGS NOTED IN THE METRO DADE
 REPORTS NUMBERED 00-0628.11, 01-0629.08
 AND99-0218.01 ARE MISSING.ALSO,
 PROVIDE ABLDG SKETCH OR TABLE DEPICTING
 THE PRESSURES FOR THE COMPONENTS AND
 CLADDING.