Plan Review Notes For Permit 01091471
Permit Number 01091471
Review Stop E
Sequence Number 20
Notes
Date Text
2003-09-19 00:00:00********** UNSAT **********************
  
 1)NOTE: PLEASE SEE SHEET E-3-3, SHOWS
 37900AMPS ON 4000A BUS DUCT AND SAME FOR
 4000A SW BRD.
  
 PLEASE SUBMIT THE ABVOE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]