Plan Review Notes
Plan Review Notes For Permit 01091471
Permit Number 01091471
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2002-02-26 00:00:00A) PLEASE INDICATE ON THE DRAWINGS
 THAT THE TRASH CHUTE CAP WILL BE AT
 LEAST THREE FEET ABOVE THE ROOF OF
 THE BUILDING. RE: NFPA 82, SECTION
 3-2.2.4.
 B) THE TRASH ROOM MUST BE AT LEAST
 TWO HOUR RATED WITH OPENING PROTECTIVES
 OF AT LEAST 1 1/2 RATINGS. RE: NFPA
 82, SECTION 3-2.4.3.
 C) IT APPEARS THAT A PORTION OF THE
 UNDERGROUND FIRE LINE RUNS UNDERNEATH
 THE BUILDING'S FOUNDATION. THIS IS
 NOT PERMITTED. RE: NFPA 24, SECTION
 8-3.1.
 D) ADDRESS REQUIRED ON BUILDING.
 E) CANVAS CANOPIES ARE TO BE FIRE
 RETARDANT.
 F) ROOF MANIFOLDS ARE REQUIRED ON THE
 ROOF. THE PLANS MAKE AT LEAST ONE
 REFERENCE TO FIRE DEPARTMENT CONNECTIONS
 BEING LOCATED ON THE ROOF.
 G) THE FIREFIGHTERS SMOKE CONTROL OR
 REMOVAL PANEL SHOULD BE LABELED WITH
 STAIRWELL LOCATIONS AND ANY OTHER
 LABELS THAT HELP PUT THE BUILDING INTO
 SOME ORIENTATION WITH REGARDS TO LAYOUT.
 H) CORRIDOR ARCH SECTION DISPLAYS
 6'- 8" HEIGHT. PLEASE VERIFY WITH
 BUILDING OFFICIALS IF THIS IS
 ACCEPTABLE.
 I) DOES UNIT A-2, UNIT C HAVE PIPE
 CHASES.
 J) THE PLAN REVIEW RESPONSE ITEM 20
 SHOULD BE AN ALERT TONE, FOLLOWED BY
 "AN EMERGENCY HAS BEEN REPORTED IN THE
 BUILDING, PLEASE LEAVE THE BUILDING,
 VIA THE EXITS, DO NOT USE THE ELEVATORS
 FOLLOWED AGAIN BY THE ALERT TONE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497