2002-02-26 00:00:00 | A) PLEASE INDICATE ON THE DRAWINGS |
| THAT THE TRASH CHUTE CAP WILL BE AT |
| LEAST THREE FEET ABOVE THE ROOF OF |
| THE BUILDING. RE: NFPA 82, SECTION |
| 3-2.2.4. |
| B) THE TRASH ROOM MUST BE AT LEAST |
| TWO HOUR RATED WITH OPENING PROTECTIVES |
| OF AT LEAST 1 1/2 RATINGS. RE: NFPA |
| 82, SECTION 3-2.4.3. |
| C) IT APPEARS THAT A PORTION OF THE |
| UNDERGROUND FIRE LINE RUNS UNDERNEATH |
| THE BUILDING'S FOUNDATION. THIS IS |
| NOT PERMITTED. RE: NFPA 24, SECTION |
| 8-3.1. |
| D) ADDRESS REQUIRED ON BUILDING. |
| E) CANVAS CANOPIES ARE TO BE FIRE |
| RETARDANT. |
| F) ROOF MANIFOLDS ARE REQUIRED ON THE |
| ROOF. THE PLANS MAKE AT LEAST ONE |
| REFERENCE TO FIRE DEPARTMENT CONNECTIONS |
| BEING LOCATED ON THE ROOF. |
| G) THE FIREFIGHTERS SMOKE CONTROL OR |
| REMOVAL PANEL SHOULD BE LABELED WITH |
| STAIRWELL LOCATIONS AND ANY OTHER |
| LABELS THAT HELP PUT THE BUILDING INTO |
| SOME ORIENTATION WITH REGARDS TO LAYOUT. |
| H) CORRIDOR ARCH SECTION DISPLAYS |
| 6'- 8" HEIGHT. PLEASE VERIFY WITH |
| BUILDING OFFICIALS IF THIS IS |
| ACCEPTABLE. |
| I) DOES UNIT A-2, UNIT C HAVE PIPE |
| CHASES. |
| J) THE PLAN REVIEW RESPONSE ITEM 20 |
| SHOULD BE AN ALERT TONE, FOLLOWED BY |
| "AN EMERGENCY HAS BEEN REPORTED IN THE |
| BUILDING, PLEASE LEAVE THE BUILDING, |
| VIA THE EXITS, DO NOT USE THE ELEVATORS |
| FOLLOWED AGAIN BY THE ALERT TONE. |
| |
| MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| 659-8096,EXT.8497 |
| 835-2910 |