Plan Review Notes
Plan Review Notes For Permit 01091471
Permit Number 01091471
Review Stop B
Sequence Number 2
Notes
Date Text
2002-02-25 00:00:00THE UL 505 CONSTRUCTION DECLARED ON
 SHEET A.28 SECTION 5 DOES NOT APPEAR TO
 BE PRACTICAL FOR SHAFT CONSTRUCTION IN
 THE CONFIGURATION DEPICTED ON THE
 PLANS.HOW WILL THE JOINTS BE TAPED ON
 THE INTERIOR OF THE SHAFTS AND THE
 ANGLES ATTACHED?
  
 DETAILS 4/A.27 AND S2.3, WHAT IS THE
 MATERIAL SHOWN AS "SM WRC 2X6"?
  
 PROVIDE SPECIFIC CONSTRUCTION DETAILS
 INCLUDING CONNECTIONS FOR THE SUSPENDED
 STUD CEILING SYSTEM SHOWN IN SECTION 3,
 SHEET A.09.
  
 SHEET A35, NOTE 1.04 B, CALLS OUT ASCE
 7-93, THE DESIGN PRESSURES IN NOTE
 2.02ADO NOT AGREE WITH THOSE ON SHEETS
 A12 - A14, ROOFING NOTES 1D ARE
 ASCE7-93.SHEET M8 DECLARES THE SOUTH
 FLORIDA BUILDING CODE AND THE
 SPECIFICATIONS STILL REFERENCE A 110
 MPH WIND DESIGN.PLEASE REVISE AS
 NECESSARY AND ENSURE COMPLIANCE WITH
 ASCE 7-95 IN ACCORDANCE WITH SBC 1606.1.
 1
  
 THE INFORMATION PROVIDED ON 2/6/02 DOES
 NOT QUALIFY THE "DYPLAST" MATERIAL AS
 NON-COMBUSTIBLE AS PROVIDED FOR IN SBC
 202. THE "ACROCRETE" PRODUCTS MAY ONLY
 BE USED IN ACCORDANCE WITH ITS LISTING
 AND LIMITATIONS CONTAINED IN THAT
 REPORT.