Plan Review Notes
Plan Review Notes For Permit 01091471
Permit Number 01091471
Review Stop E
Sequence Number 13
Notes
Date Text
2003-07-16 00:00:00************* UNSAT *****************
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM
 AND PANELS.
 THERE ARE NUMEROUS LOCATIONS THAT
 FEEDERS SIZES DO NOT SEEM TO CORRELATE
 AND SOME DO NOT MEET 310-16 FOR SIZING
 AND OCP UNDER 240.
  
 PLEASE PROVIDE A CURRENT AND UP TO DATE
 COMPLETE RISER DIAGRAM AND ALL PANEL
 SCHEDULES.
 IF THERE ARE ANY QUESTIONS,PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717