Plan Review Notes
Plan Review Notes For Permit 01091471
Permit Number 01091471
Review Stop B
Sequence Number 10
Notes
Date Text
2002-12-11 00:00:00RE: ROOF TILE NOA 99-1012.01.
  
 THE NOA HAS HIGH LIGHTED ON IT TABEL 4A
 FOR A SINGLE PATTY ADHESIVE SYSTEM.
  
 SECTION 3 LIMITATIONS, REQUIRES A
 STATIC FIELD UPLIFT TEST IN ACCORDANCE
 WITH MIAMI DADE RAS 106.THE RESULTS
 OF THIS TESTING MUST BE PROVIDED TO THE
 CITY.
  
 DOCUMENTATION OF THE QUARTERLY TESTING
 AS SET OUT IN THE REPORT MUST ALSO BE
 PROVIDED TO THE CITY.
  
 PRIOR TO ANY INSTALLATION, AN ANALYSIS
 IN ACCORDANCE WITH MIAMI-DADE RAS 127
 FOR A MOMENT BASED SYSTEM USING THE
 PRESSURE FOR THE CORNER ZONE MUST BE
 BE PROVIDED BY G.V. PIREZ, PE.THE
 SHEET DATED 9/15/01 HAS PRESSURES OF
 -112 FOR ZONE 1 AND -182 FOR ZONE 2.
 THE CORNERS OR ZONE THREE ARE ABSENT
 FROM THAT SHEET AND THE MR APPEARS
 MARGINAL.