Plan Review Notes
Plan Review Notes For Permit 01091471
Permit Number 01091471
Review Stop P
Sequence Number 1
Notes
Date Text
2001-10-20 00:00:00PLUMBING PLAN REVIEW,DENIED
 CODE REFERENCE,STD PLUMBING CODE 94
 (1)SHT A20,NOTE 7,FACBC-97 NOT APPROVED
 COMPLY WITH FAIR HOUSING ACT 24 CODE OF
 REGULATION (CFR) 100.205 (C)(IV),
 REVISED APRIL 1998, DESIGN MANUAL.
 REQUIRMENTS 1 THRU 7,SPECIFY OPTION "A"
 OR "B". SHOW MANEUVERING AND CLEAR FLOOR
 SPACE, REQUIRMENT 7 AND REINFORCED WALL
 AREAS, AS OUT LINED IN DESIGN MANUAL.
 (2) SHT A28 DETAIL 4,PROVIDE A ISOMETRIC
 DRAWING OF ROOF DRAINAGE WITH PIPE SIZES
 , SQUARE FOOTAGE; ALSO INCLUDE 1/2 THE
 VERTIAL WALLS AND UPPER ROOFS.
 PROVIDE CALCULATIONS FOR THE SECONDARY
 DRAINAGE, INCLUDE 1/2 THE VERTIAL WALLS
 AND UPPER ROOFS. SEC 1108,1108.3,1109.
 (3A)SHT P1 PROVIDE A COMPLETE PLAN VIEW
 OF THE UNDER GROUND STORM AND SANITARY
 BUILDING DRAINAGE SYSTEM,SHOW PIPE SIZES
 AND THE LOAD ON EACH SYSTEM, SEC 104.3
 (B) TRASH ROOM DRAIN NOT APPROVED TO
 STORM DRAINAGE. SEC 701.5
 (C) SANITARY BUILDING DRAINS, 4" THRU 6"
 CLEANOUTS NOT MORE THAN 80 FT INTERVALS.
 SEC 710.2.4 (2)
 (4) SHT P6 SPECIFY TYPE OF SHOCK
 ARRESTOR AND TABLE FOR SIZING, SEC 104.3
 (5) SHT P 12 NOTE #10 RELIEF VENT, SHOW
 VENTS ON RISER,SHTS P8,P9. SEC 104.3 AND
 SEC 916.
 END OF COMMENTS PAUL SCHMITZ
 QUESTIONS 561-659-8096X 8233