2001-10-20 00:00:00 | PLUMBING PLAN REVIEW,DENIED |
| CODE REFERENCE,STD PLUMBING CODE 94 |
| (1)SHT A20,NOTE 7,FACBC-97 NOT APPROVED |
| COMPLY WITH FAIR HOUSING ACT 24 CODE OF |
| REGULATION (CFR) 100.205 (C)(IV), |
| REVISED APRIL 1998, DESIGN MANUAL. |
| REQUIRMENTS 1 THRU 7,SPECIFY OPTION "A" |
| OR "B". SHOW MANEUVERING AND CLEAR FLOOR |
| SPACE, REQUIRMENT 7 AND REINFORCED WALL |
| AREAS, AS OUT LINED IN DESIGN MANUAL. |
| (2) SHT A28 DETAIL 4,PROVIDE A ISOMETRIC |
| DRAWING OF ROOF DRAINAGE WITH PIPE SIZES |
| , SQUARE FOOTAGE; ALSO INCLUDE 1/2 THE |
| VERTIAL WALLS AND UPPER ROOFS. |
| PROVIDE CALCULATIONS FOR THE SECONDARY |
| DRAINAGE, INCLUDE 1/2 THE VERTIAL WALLS |
| AND UPPER ROOFS. SEC 1108,1108.3,1109. |
| (3A)SHT P1 PROVIDE A COMPLETE PLAN VIEW |
| OF THE UNDER GROUND STORM AND SANITARY |
| BUILDING DRAINAGE SYSTEM,SHOW PIPE SIZES |
| AND THE LOAD ON EACH SYSTEM, SEC 104.3 |
| (B) TRASH ROOM DRAIN NOT APPROVED TO |
| STORM DRAINAGE. SEC 701.5 |
| (C) SANITARY BUILDING DRAINS, 4" THRU 6" |
| CLEANOUTS NOT MORE THAN 80 FT INTERVALS. |
| SEC 710.2.4 (2) |
| (4) SHT P6 SPECIFY TYPE OF SHOCK |
| ARRESTOR AND TABLE FOR SIZING, SEC 104.3 |
| (5) SHT P 12 NOTE #10 RELIEF VENT, SHOW |
| VENTS ON RISER,SHTS P8,P9. SEC 104.3 AND |
| SEC 916. |
| END OF COMMENTS PAUL SCHMITZ |