Plan Review Notes
Plan Review Notes For Permit 01091471
Permit Number 01091471
Review Stop M
Sequence Number 1
Notes
Date Text
2001-10-17 00:00:00********************DENIED**************
  
 1.PROVIDE CLARIFICATION OF THE SMOKE
 EVAC FOR THE CORRIDORS ON FLOORS 2
 THRU 15.NOTE ON PLAN SHEET M-8
 INDICATE RTU 1 & 2 FAN MOTOR WILL
 CONTINUE TO RUN. PROVIDE SEQUENCE OF
 OPERATION FOR THE MOTORZIED DAMPERS
 INDICATED ON PLAN SHEET M-4.
  
 2.PROVIDE INFORMATION FOR SEQUENCE OF
 OPERATION FOR GROUND FLOOR SMOKE
 EVAC.
  
 3.PROVIDE CALCULATIONS AS PER 1997
 SBC 412.5.
  
 4.PROVIDE INFORMATION AS TO THE GROUND
 FLOOR RETURN AIR PLENUM.PLAN SHEET
 M-7 INDICATES RETURN AIR GRILLS IN
 THE VARIOUS OFFICES AND FITNESS
 CENTER.THERE IS NO INDICATION HOW
 THE AIR IS BEING RETURNED BACK TO
 THE AIR HANDLER BE MEANS OF DUCTWORK
 OR TRANSFER DUCTS.
  
 5.CLARIFY ALSO IF THESE AREAS WERE
 TAKEN INTO CONSIDERATION IN THE
 DESIGN OF THE SMOKE EVAC TO THIS
 FLOOR.
  
 6.SUBMIT TEST CRITERIA FOR THE SMOKE
 EVAC SYSTEM.
  
 7.ONLY ONE FIRE DAMPER IS DESIGNATED
 ON THE GROUND FLOOR.THE CORRIDOR
 LOOKS TO HAVE A FIRE RATING OF 1 HR.
 EXPLAIN WHY THE OTHER PENETRATIONS
 ARE NOT PROTECTED.
  
 8.PROVIDE CALCULATIONS FOR STAIRWELL
 PRESSURIZATION.
  
 PLEASE NOTE, STAIRWELL PRESSURIZATION
 SHALL BE TESTED WITH ALL DOORS CLOSED
 AND ALSO WITH ONE EXTERIOR DOOR PROPPED
 OPEN APPROXIMATELY 5" SIMULATING PEOPLE
 EXITING IN AN EMERGENCY SITUATION.AN
 INDEPENDANT TEST AND BALANCE COMPANY AND
 THE ENGINEER OF RECORD SHOULD ATTEND THE
 FINAL TESTING.
  
 9.PROVIDE RISER DIAGRAM FOR SPRINKLER
 SYSTEM FOR INDICATING LOCATION OF
 SPRINKLER HEADS AND ACCESS DOORS
 FOR MAINTENANCE FOR THE TRASH CHUTE
 AS WELL AS THE DRYER VENT SHAFT.
 1997 SBC 705.4.2.6.
  
 10. PLEASE CLARIFY SEPARATION OF DRYER
 EXHAUST AND TOILET EXHAUST SHARING
 THE 2 HOUR RATED SHAFT.PROVIDE A
 DETAIL SHOWING HOW THE SUB-DUCT IS
 SUPPORTED IN THE SHAFT.
  
 11. PLEASE NOTE THE ACCESS DOOR ON PLAN
 SHEET M-10 FOR THE DRYER EXHAUST IS
 NOT ACCESSIBLE.
  
 12. PROVIDE INFORMATION ON HOW THE
 COMBUSTIBLE LINT IS TO BE REMOVED
 FROM THE SHAFT.
  
 13. PLAN SHEET M-3, CLARIFY THE EXHAUST
 DUCT RUNNING THRU OR TERMINATING IN
 THE STAIRWELL.
  
 14. M-3, ON THE SOUTHEAST ROOF THE
 DRYER VENT CLOSE PROXIMTY TO THE
 CONDENSER UNITS.
  
 15. PLAN SHEET M-12 FAN COIL UNIT
 MOUNTING DETAIL, AUXILIARY DRAIN PAN
 WITH OVERFLOW PROTECTION BY MEANS OF
 A FLOAT SWITCH A SEPARATE DRAIN
 TERMINATING AT A CONSPICUOUS POINT
 TO SERVE AS AN ALARM THAT REGULAR
 LINE IS RESTRICTED. 1997 SMC
 304.8.6.1.
  
 16. PLAN SHEET M-13 DETAIL OF CONDENSING
 UNIT SUPPORTS.MINIMUM OF 18"
 BETWEEN THE ROOF SURFACE AND THE
 BOTTOM OF THE SUPPORT RAIL AS PER
 COUNTYWIDE AMENDMENTS 1997 SMC
 304.2.5.
  
 17. CONDENSER UNIT LOCATION SHALL COMPLY
 WITH 1997 SMC 304.7.2, A MINIMUM OF
 30" OF CLEAR SPACE ON THE SERVICE
 SIDE FOR INSPECTION AND SERVICING OF
 CONDENSING UNITS OR COMPRESSOR UNITS
 SHALL BE PROVIDED.
  
 18. PROVIDE LOCATION OF FUEL TANK.
  
 19. ADDITIONAL PERMIT REQUIRED FOR FUEL.
 PLEASE PROVIDE PLANS WITH PERMIT
 APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.