2001-10-17 00:00:00 | ********************DENIED************** |
| |
| 1.PROVIDE CLARIFICATION OF THE SMOKE |
| EVAC FOR THE CORRIDORS ON FLOORS 2 |
| THRU 15.NOTE ON PLAN SHEET M-8 |
| INDICATE RTU 1 & 2 FAN MOTOR WILL |
| CONTINUE TO RUN. PROVIDE SEQUENCE OF |
| OPERATION FOR THE MOTORZIED DAMPERS |
| INDICATED ON PLAN SHEET M-4. |
| |
| 2.PROVIDE INFORMATION FOR SEQUENCE OF |
| OPERATION FOR GROUND FLOOR SMOKE |
| EVAC. |
| |
| 3.PROVIDE CALCULATIONS AS PER 1997 |
| SBC 412.5. |
| |
| 4.PROVIDE INFORMATION AS TO THE GROUND |
| FLOOR RETURN AIR PLENUM.PLAN SHEET |
| M-7 INDICATES RETURN AIR GRILLS IN |
| THE VARIOUS OFFICES AND FITNESS |
| CENTER.THERE IS NO INDICATION HOW |
| THE AIR IS BEING RETURNED BACK TO |
| THE AIR HANDLER BE MEANS OF DUCTWORK |
| OR TRANSFER DUCTS. |
| |
| 5.CLARIFY ALSO IF THESE AREAS WERE |
| TAKEN INTO CONSIDERATION IN THE |
| DESIGN OF THE SMOKE EVAC TO THIS |
| FLOOR. |
| |
| 6.SUBMIT TEST CRITERIA FOR THE SMOKE |
| EVAC SYSTEM. |
| |
| 7.ONLY ONE FIRE DAMPER IS DESIGNATED |
| ON THE GROUND FLOOR.THE CORRIDOR |
| LOOKS TO HAVE A FIRE RATING OF 1 HR. |
| EXPLAIN WHY THE OTHER PENETRATIONS |
| ARE NOT PROTECTED. |
| |
| 8.PROVIDE CALCULATIONS FOR STAIRWELL |
| PRESSURIZATION. |
| |
| PLEASE NOTE, STAIRWELL PRESSURIZATION |
| SHALL BE TESTED WITH ALL DOORS CLOSED |
| AND ALSO WITH ONE EXTERIOR DOOR PROPPED |
| OPEN APPROXIMATELY 5" SIMULATING PEOPLE |
| EXITING IN AN EMERGENCY SITUATION.AN |
| INDEPENDANT TEST AND BALANCE COMPANY AND |
| THE ENGINEER OF RECORD SHOULD ATTEND THE |
| FINAL TESTING. |
| |
| 9.PROVIDE RISER DIAGRAM FOR SPRINKLER |
| SYSTEM FOR INDICATING LOCATION OF |
| SPRINKLER HEADS AND ACCESS DOORS |
| FOR MAINTENANCE FOR THE TRASH CHUTE |
| AS WELL AS THE DRYER VENT SHAFT. |
| 1997 SBC 705.4.2.6. |
| |
| 10. PLEASE CLARIFY SEPARATION OF DRYER |
| EXHAUST AND TOILET EXHAUST SHARING |
| THE 2 HOUR RATED SHAFT.PROVIDE A |
| DETAIL SHOWING HOW THE SUB-DUCT IS |
| SUPPORTED IN THE SHAFT. |
| |
| 11. PLEASE NOTE THE ACCESS DOOR ON PLAN |
| SHEET M-10 FOR THE DRYER EXHAUST IS |
| NOT ACCESSIBLE. |
| |
| 12. PROVIDE INFORMATION ON HOW THE |
| COMBUSTIBLE LINT IS TO BE REMOVED |
| FROM THE SHAFT. |
| |
| 13. PLAN SHEET M-3, CLARIFY THE EXHAUST |
| DUCT RUNNING THRU OR TERMINATING IN |
| THE STAIRWELL. |
| |
| 14. M-3, ON THE SOUTHEAST ROOF THE |
| DRYER VENT CLOSE PROXIMTY TO THE |
| CONDENSER UNITS. |
| |
| 15. PLAN SHEET M-12 FAN COIL UNIT |
| MOUNTING DETAIL, AUXILIARY DRAIN PAN |
| WITH OVERFLOW PROTECTION BY MEANS OF |
| A FLOAT SWITCH A SEPARATE DRAIN |
| TERMINATING AT A CONSPICUOUS POINT |
| TO SERVE AS AN ALARM THAT REGULAR |
| LINE IS RESTRICTED. 1997 SMC |
| 304.8.6.1. |
| |
| 16. PLAN SHEET M-13 DETAIL OF CONDENSING |
| UNIT SUPPORTS.MINIMUM OF 18" |
| BETWEEN THE ROOF SURFACE AND THE |
| BOTTOM OF THE SUPPORT RAIL AS PER |
| COUNTYWIDE AMENDMENTS 1997 SMC |
| 304.2.5. |
| |
| 17. CONDENSER UNIT LOCATION SHALL COMPLY |
| WITH 1997 SMC 304.7.2, A MINIMUM OF |
| 30" OF CLEAR SPACE ON THE SERVICE |
| SIDE FOR INSPECTION AND SERVICING OF |
| CONDENSING UNITS OR COMPRESSOR UNITS |
| SHALL BE PROVIDED. |
| |
| 18. PROVIDE LOCATION OF FUEL TANK. |
| |
| 19. ADDITIONAL PERMIT REQUIRED FOR FUEL. |
| PLEASE PROVIDE PLANS WITH PERMIT |
| APPLICATION. |
| |