Plan Review Notes
Plan Review Notes For Permit 01091471
Permit Number 01091471
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-10-09 00:00:001) SITE PLAN DOES NOT INDICATE FIRE
 HYDRANT LOCATIONS.
 2) A DETERMINATION WILL BE REQUIRED BY
 THE BUILDING OFFICIAL OR HIS DESIGNEE
 WITH REGARDS TO THE COVERED WALKWAY.
 FS 553.895 (2) EXEMPTS AN OPEN PARKING
 GARAGE WITH A 20 FOOT SEPARATION FROM
 BEING FIRE SPRINKLER PROTECTED. THE
 COVERED PEDESTRIAN WALKWAY APPEARS TO
 CONNECT BOTH THE PARKING GARAGE AND THE
 HIGH-RISE BUILDING.
 3) A KNOX-BOX WILL BE REQUIRED FOR FIRE
 ACCESS.
 4) BUILDING ADDRESS REQUIRED PER CITY
 CODE 3343-00.
 5) PLEASE CLARIFY WELL COMPACTED FIELD
 FOR FIRE TRUCK ACCESS.
 6) A TEMPORARY STANDPIPE SYSTEM WILL
 BE REQUIRED WHEN CONSTRUCTION REACHES
 THREE STORIES AND FIFTY FEET.
 7) STAIRS ARE TO BE CONTINIOUS WITH
 CONSTRUCTION.
 8) PLEASE DEMONSTRATE COMPLIANCE WITH
 THE STETCHER REQUIREMENTS OF 1997
 STANDARD BUILDING CODE.
 9) PLEASE EXPLAIN HOW ALL OF THE
 REQUIRED DEVICES FOR THE FIRE COMMAND
 CENTER ARE GOING TO FIT INTO THE
 CLOSET PROVIDED. PLEASE SEE 1997
 STANDARD BUILDING CODE.
 10) PLEASE DEMONSTRATE COMPLIANCE FOR
 SMOKE CONTROL REQUIREMENTS OF 1997
 STANDARD BUILDING CODE.
 11) SIGNS ARE REQUIRED FOR STAIRWAYS
 INDICATING FLOOR LEVEL, TERMINUS TOP
 AND BOTTOMS AND THE IDENTITY OF THE
 STAIRS.
 12) PLEASE INDICATE WHAT PROVISIONS
 HAVE BEEN MADE FOR FIRE RESCUE ACCESS
 FOR THE NORTH AND SOUTH GATES. WILL
 THESE GATES BE ELECTRIC OR MANUALLY
 OPERATED. IF ELECTRIC IS BATTERY
 BACK-UP AVAILABLE. SEPARATE PLANS
 AND PERMITS REQUIRED FOR SECURITY GATES.
 13) SITE PLAN DOES NOT INDICATE THE
 LOCATION OF THE ABOVEGROUND FUEL TANK
 SHOWN ON PAGE P-12.
 14) NO FIRE DEPARTMENT CONNECTIONS
 SHOWN ON FP-1. SINCE THE BUILDING IS
 CONSIDERED HIGH-RISE, TWO FIRE
 DEPARTMENT CONNECTIONS WILL BE REQUIRED.
 15) AREA DIRECTLY NEXT TO ELECTRICAL
 ROOM DISPLAYS NO FIRE SPRINKLER
 PROTECTION. WHAT IS THIS AREA USED FOR.
 16) INTERIOR FINISH INFORMATION
 REQUIRED FOR WALLS AND CEILINGS OF
 BUILDINGS.
 17) PLEASE INDICATE THAT ATTIC SPACES
 WILL NOT BE USED FOR STORAGE.
 18) HOW IS COMBUSTIBLE LINT REMOVED
 FROM THE DRYER EXHAUST RISERS.
 19) NO SMOKE DETECTORS SHOWN IN
 SLEEPING ROOMS.
 20) PLEASE INDICATE WHAT THE VOICE
 EVACUATION MESSAGE OF THE FIRE ALARM
 SYSTEM WILL SAY.
 21) ELECTRICAL DRAWINGS APPEAR TO BE
 INCOMPLETE.
 22) PLEASE PROVIDE MORE DETAILS ON
 SMOKE EVACUATION SYSTEM FOR THE STAIR
 TOWERS AND IDENTIFY THAT THESE SYSTEMS
 WILL BE ON EMERGENCY POWER.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910