Plan Review Notes
Plan Review Notes For Permit 01091471
Permit Number 01091471
Review Stop E
Sequence Number 1
Notes
Date Text
2001-10-24 00:00:00**************** UNSAT *****************
  
  
 1)NOTE: PLEASE NOTE THAT IN ORDER TO DO
 A COMPLETE PLAN REVIEW. PLANS NEED TO
 BE COMPLETE. GAZEBO IS MISSING,GENERATOR
 LOACTION, MISSING ELECTRICAL ROOM DETAIL
 -S FOR FLOOR WITH HOUSE PANELS?
  
 2)NOTE: PLEASE NOTE TWO FLOORS SHOWING
 HOUSE PANELS 4E AND 4H?
  
 3)NOTE: PLEASE NOTE THAT CIRCUIT LAYOUT
 ON LOWER CORNER OF E1-2 DOES NOT
 CORRELATE WITH E3-1?
  
 4)NOTE: PLEASE NOTE MEANS OF BEING ABLE
 TO SHUT DOWN GENERATOR TO BE GROUPED
 WITH MAINS? 230-72, 230-76,230-79
  
 5)NOTE: PLEASE NOTE THAT FIRE PUMP ROOM
 IS SHOWN ON SECOND FLOOR, WHERE IS MAIN
 ELECTRICAL ROOM?
  
 6)NOTE: PLEASE NOTE COMPLETE CONCRETE
 ENCASEMENT OF SERVICE ENTRANCE CONDUCTOR
 S, NO MORETHAN 8' OF UNPROTECTED CONDUCT
 -ORS INSIDE THE BLDG. PER LOCAL AMEND.
 230-70A
  
 7)NOTE: PLEASE NOTE PANEL "A" NOT
 COMPLETED.
  
 8)NOTE: PLEASE NOTE NO OCP SHOWN FOR
 ALL MAINS FOR APT PANELS???
  
 9)NOTE: PLEASE NOTE, ON E3-2 RISER SHOWS
 12H AND 12E AND YET E3-1 DOES NOT SHOW
 WHERE THESE ARE FED FROM? PANEL "DE"
 DOES NOT SHOW?
  
 10)NOTE: PLEASE NOTE GROUNDING ELECTRODE
 CONDUCTOR SIZE PER 250-66 NEEDS TO BE
 SHOWN ON E3-3
  
 PLEASE NOTE THAT THERE ARE MANY ITEMS
 ON E3-1 THAT NEED TO BE ADDRESSED.
  
 11)NOTE: PLEASE NOTE NO OCP SHOWN FOR
 FIRE PUMP, FROM FIRE PUMP CONTROL PANEL,
 AND FIRE PUMP ATS.
  
 12)NOTE: PLEASE NOTE CONDUCTOR TO FIRE
 PUMP ARE SHOWN AT 250MCM??, PLEASE SEE
 SIZING PER LOAD OF PUMP 430-150 AND
 CONDCUTOR SIZES PER 310-16.
  
 13)NOTE: PLEASE NOTE OCP PER 695-4-B-1
  
 14)NOTE: PLEASE NOTE THAT OCP ON GENER-
 -ATOR IS SHOWN AT 500AMPS WITH 250MCM??
 310-16.
  
 15)NOTE: PLEASE NOTE THAT CONDCUTOR SIZE
 FOR 400A ATS MAIN IS SHOWN AT 4/0?
 310-16 FOR 400AMPS, ALSO 350MCM FROM
 ATS TO PANEL "DE" ON 400A OCP??
  
 16)NOTE: PLEASE NOTE THAT NO CONDCUTOR
 SIZE IS SHOWN COMING FROM FPL TO 600A
 PANEL"DH"???
  
 17)NOTE: PLEASE NOTE THAT THERE ARE NO
 VOLTAGES SHOWN FOR PANEL"DH" ON PANEL
 SCHEDULE.
  
 18)NOTE:PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PANEL"DH" "DE" ETC
  
 19)NOTE: PLEASE NOTE THAT THERE ARE NO
 PANEL SCHEDULES SUBMITTED FOR ALL HOUSE
 PANELS, NOT TO INCLUDE CIRCUIT SCHEDULE
 ON E1-2.
  
 21)NOTE:PLEASE NOTE THAT THE GENERATOR
 IS TO BE SIZED PER 695-B-1. PLEASE
 NOTE THAT LOAD EXCEEDS RATING OF GEN.
 PLEASE CLARIFY HOW AUTOMATIC SHEDDING
 OF LOADS WILL TAKE PLACE???
  
 22)NOTE: PLEASE PLACE NOTE ON PLANS FOR
 COLOR CODING OF FEDDERS PER LOCAL
 AMENDMENTS 215-8 277/480V BR/PURP/YELLOW
 GRAY, 120/208 BLK/RED/BLUE.
  
 23)NOTE: PLEASE CLARIFY GROUNDING SIZE
 OF CONDCUCTOR FOR GENERATOR AS #4,???
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL. PLEASE CALL TO SET UP A
 MEETING IN PERSON TO CLARIFY ITEMS THAT
 MAY BE MORE CLEAR IN PERSON.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372