2001-10-24 00:00:00 | **************** UNSAT ***************** |
| |
| |
| 1)NOTE: PLEASE NOTE THAT IN ORDER TO DO |
| A COMPLETE PLAN REVIEW. PLANS NEED TO |
| BE COMPLETE. GAZEBO IS MISSING,GENERATOR |
| LOACTION, MISSING ELECTRICAL ROOM DETAIL |
| -S FOR FLOOR WITH HOUSE PANELS? |
| |
| 2)NOTE: PLEASE NOTE TWO FLOORS SHOWING |
| HOUSE PANELS 4E AND 4H? |
| |
| 3)NOTE: PLEASE NOTE THAT CIRCUIT LAYOUT |
| ON LOWER CORNER OF E1-2 DOES NOT |
| CORRELATE WITH E3-1? |
| |
| 4)NOTE: PLEASE NOTE MEANS OF BEING ABLE |
| TO SHUT DOWN GENERATOR TO BE GROUPED |
| WITH MAINS? 230-72, 230-76,230-79 |
| |
| 5)NOTE: PLEASE NOTE THAT FIRE PUMP ROOM |
| IS SHOWN ON SECOND FLOOR, WHERE IS MAIN |
| ELECTRICAL ROOM? |
| |
| 6)NOTE: PLEASE NOTE COMPLETE CONCRETE |
| ENCASEMENT OF SERVICE ENTRANCE CONDUCTOR |
| S, NO MORETHAN 8' OF UNPROTECTED CONDUCT |
| -ORS INSIDE THE BLDG. PER LOCAL AMEND. |
| 230-70A |
| |
| 7)NOTE: PLEASE NOTE PANEL "A" NOT |
| COMPLETED. |
| |
| 8)NOTE: PLEASE NOTE NO OCP SHOWN FOR |
| ALL MAINS FOR APT PANELS??? |
| |
| 9)NOTE: PLEASE NOTE, ON E3-2 RISER SHOWS |
| 12H AND 12E AND YET E3-1 DOES NOT SHOW |
| WHERE THESE ARE FED FROM? PANEL "DE" |
| DOES NOT SHOW? |
| |
| 10)NOTE: PLEASE NOTE GROUNDING ELECTRODE |
| CONDUCTOR SIZE PER 250-66 NEEDS TO BE |
| SHOWN ON E3-3 |
| |
| PLEASE NOTE THAT THERE ARE MANY ITEMS |
| ON E3-1 THAT NEED TO BE ADDRESSED. |
| |
| 11)NOTE: PLEASE NOTE NO OCP SHOWN FOR |
| FIRE PUMP, FROM FIRE PUMP CONTROL PANEL, |
| AND FIRE PUMP ATS. |
| |
| 12)NOTE: PLEASE NOTE CONDUCTOR TO FIRE |
| PUMP ARE SHOWN AT 250MCM??, PLEASE SEE |
| SIZING PER LOAD OF PUMP 430-150 AND |
| CONDCUTOR SIZES PER 310-16. |
| |
| 13)NOTE: PLEASE NOTE OCP PER 695-4-B-1 |
| |
| 14)NOTE: PLEASE NOTE THAT OCP ON GENER- |
| -ATOR IS SHOWN AT 500AMPS WITH 250MCM?? |
| 310-16. |
| |
| 15)NOTE: PLEASE NOTE THAT CONDCUTOR SIZE |
| FOR 400A ATS MAIN IS SHOWN AT 4/0? |
| 310-16 FOR 400AMPS, ALSO 350MCM FROM |
| ATS TO PANEL "DE" ON 400A OCP?? |
| |
| 16)NOTE: PLEASE NOTE THAT NO CONDCUTOR |
| SIZE IS SHOWN COMING FROM FPL TO 600A |
| PANEL"DH"??? |
| |
| 17)NOTE: PLEASE NOTE THAT THERE ARE NO |
| VOLTAGES SHOWN FOR PANEL"DH" ON PANEL |
| SCHEDULE. |
| |
| 18)NOTE:PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW EQUIPMENT BEING INSTALLED. |
| MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| THE AVAILABLE FAULT CURRENT PER 110-9. |
| PANEL"DH" "DE" ETC |
| |
| 19)NOTE: PLEASE NOTE THAT THERE ARE NO |
| PANEL SCHEDULES SUBMITTED FOR ALL HOUSE |
| PANELS, NOT TO INCLUDE CIRCUIT SCHEDULE |
| ON E1-2. |
| |
| 21)NOTE:PLEASE NOTE THAT THE GENERATOR |
| IS TO BE SIZED PER 695-B-1. PLEASE |
| NOTE THAT LOAD EXCEEDS RATING OF GEN. |
| PLEASE CLARIFY HOW AUTOMATIC SHEDDING |
| OF LOADS WILL TAKE PLACE??? |
| |
| 22)NOTE: PLEASE PLACE NOTE ON PLANS FOR |
| COLOR CODING OF FEDDERS PER LOCAL |
| AMENDMENTS 215-8 277/480V BR/PURP/YELLOW |
| GRAY, 120/208 BLK/RED/BLUE. |
| |
| 23)NOTE: PLEASE CLARIFY GROUNDING SIZE |
| OF CONDCUCTOR FOR GENERATOR AS #4,??? |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. PLEASE CALL TO SET UP A |
| MEETING IN PERSON TO CLARIFY ITEMS THAT |
| MAY BE MORE CLEAR IN PERSON. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-659-8096 EXT 8372 |