Plan Review Notes
Plan Review Notes For Permit 01091471
Permit Number 01091471
Review Stop B
Sequence Number 1
Notes
Date Text
2001-11-08 00:00:00PLEASE PROVIDE A RECENT PROPERTY SURVEY.
  
 THE SOIL REPORT IS REQUIRED TO HAVE THE
 EMBOSSED SEAL OF THE ENGINEER TOGETHER
 WITH THE ORIGINAL SIGNATURE AND DATE.
 THIS IS REQUIRED FOR ALL DOCUMENTS
 PREPARED BY AN ENGINEER OR ARCHITECT
 AND SUBMITTED FOR PUBLIC RECORD.SEE
 FS 471 AND 481
  
 PLEASE PROVIDE THE FIRE DESIGN NUMBERS
 FOR THE MASONRY WALLS SERVING AS SHAFT
 ENCLOSURES AND EXTERIOR WALLS.SEE SBC
 701.5.
  
 WHAT IS THE MEANING OF THE NOTE ON
 SHEETA0-1 "ADJACENT BUILDING WALL
 CONSTRUCTED AS FIRE WALL AS DEFINED BY
 CODE." ?
  
 THE DOORS TO THE CLUBHOUSE AND FITNESS
 ROOMS SHOWN AS #26 ARE REQUIRED TO BE
 FIRE RATED.SEE SBC 705.1.2 AND
 704.1.1.
  
  
 SBC 1008 REQUIRES ONE OF THE EXIT STAIRS
 TO BE CONTINUOUS TO THE ROOF.
  
 SBC 3104.3 REQUIRES "PROTECTION AT THE
 INTERFACE" WHERE THE COVERED WALKWAY
 JOINS THE BUILDING.
  
 NEITHER THE PLANS NOR THE SPECIFICATIONS
 INDICATE THE USE OF FIRE RETARDANT
 TREATED, (FRT) BLOCKING AS PROVIDED FOR
 IN SBC 609 AND SBC 707.1.
  
 SBC 104.2.1 DOES NOT ALLOW CITING THE
 CODE IN LIEU OF SPECIFIC DESIGN
 INFORMATION SUCH AS THAT FOUND ON SHEET
 A-29 "ADHERE DYPLAST W/ STANDARD
 BUILDING CODE 1403.6.8 ..."WHICH IS
 NOT A VALID CODE SECTION ANYWAY, PLEASE
 REVISE AS NECESSARY.
  
 DETAIL 1/A12 ON SHEET A29. SHOW A
 SPECIFIC CONNECTION DETAIL FOR THE
 STONE CORBEL OR IF DESIGN IS
 DESIGNATED, THE LOCATION, NATURE,
 DIRECTION AND MAGNITUDE OF THE FORCES
 TO BE RESISTED.
  
 MOST OF THE PAGES IN THE STRUCTURAL
 CALCULATIONS DO NOT PERTAIN TO THIS
 BUILDING.PLEASE PROVIDE COMPLETE
 CALCULATIONS DEMONSTRATING COMPLIANCE
 WITH SBC 1601 AND NOT JUST A WIND
 RESISTANCE INVESTIGATION.
  
 SHEET S-1.1 NOTE #8, WHAT IS THE TOP OF
 FOOTING ELEVATIONS?
  
 SEE SBC 1608.2.2 FOR THE GUARDRAIL
 DESIGN LOADS SHOWN ON SHEET A27 IN
 DETAIL 5/A25.
  
 SHEET S 1-1 DEPICTS COLUMNS NUMBERED 1
 THROUGH 48 AND THE COLUMN SCHEDULE ON
 SHEET S 4-1 LISTS ONLY 42.THERE IS NO
 DETAIL FOR COLUMN #46.
  
 A THRESHOLD INSPECTION PLAN IS REQUIRED
 FOR THIS BUILDING AS PROVIDED FOR IN FS
 553.71.
  
 SEVERAL AREAS OF THE SPECIFICATIONS
 ERRONEOUSLY CITE A 110 MPH WIND SPEED.
 PLEASE REVISE AS NECESSARY AND INCLUDE
 A SKETCH OF THE BUILDING DEFINING THE
 PRESSURE ZONES AND THEIR ATTENDANT
 PRESSURES.
  
 SMOKE DETECTORS ARE NOT SHOWN INSIDE OF
 THE SLEEPING ROOMS AS PROVIDE FOR IN
 NFPA 72 WHICH IS INVOKED BY SBC 905.2.
  
 THE STAIR SECTIONS SHOWN WITH RISER
 HEIGHTS OF 6.5" OR LESS WHEN TAKEN
 TOGETHER WITH THE DECLARED 11" TREAD DO
 NOT MEET THE 24"- 25" OF SBC 1007.3.1.
 SEE ALSO NFPA 101 FOR THE 7/11
 REQUIREMENT.
  
 PLEASE PROVIDE CALCULATIONS AND A
 WRITTEN NARRATIVE TO BETTER DESCRIBE
 THE SEQUENCE OF OPERATIONS FOR SMOKE
 CONTROL DECLARED ON SHEET M-8.
 DEMONSTRATE THAT THE BAROMETRIC RELIEF
 DAMPER WILL PROVIDE FOR AT LEAST 2500
 CFM FLOWINGAND ANTICPATED STACK
 PRESSURES IN THE BUILDING.SEE SBC
 412.11 (5).
  
 DESCRIBE HOW SMOKE REMOVAL FROM THE
 CORRIDORS WILL BE ACCOMPLISHED AT A
 RATE OF AT LEAST 6 AIR CHANGES PER
 HOUR. SEE SBC 412.5 (3) IF THIS IS THE
 INTENDED METHOD.
  
 SHEET E3-5 DOES NOT SHOW THE FIRE
 DEPARTMENT COMMUNICATION SYSTEM
 REQUIRED BY SBC 412.3.3.ARE THE MARKS
 SHOWN ON THE PLANS AS [T] THE INTENDED
 LOCATIONS?
  
 E 3-5, OR THE SPECIFICATIONS, DO NOT
 SHOW THE BACKUP POWER SUPPLY FOR THE
 ALARM SYSTEM. ELEVATOR RECALL BY
 ELEVATOR LOBBY SMOKE DETECTOR IS NOT
 NOTED IN THE SEQUENCE OF OPERATION. SEE
 SBC 412.6.3.
  
 THERE IS NO SPECIFICATION FOR THE
 GENERATOR FUEL SUPPLY.SEE SBC
 412.7.1.2.ALSO THE E SHEETS DO NOT
 CLEARLY INDICATE THE MANDATORY STAND BY
 POWER LOADS TO BE CARRIED BY THE
 GENERATOR.SEE SBC 412.7.2.
  
 SEVERAL OF THE DOORS WITHIN THE UNITS DO
 NOT MEET THE NOMINAL 32" WIDTH REQUIRED
 BY THE FAIR HOUSING ACT. TOILET AND
 POWDER ROOMS, BEDROOMS, WALKIN CLOSETS,
 PATIOS, AND SIMILAR LIVING AREAS AS
 CITED IN THAT LAW.PLEASE REVISE AS
 NECESSARY.
  
 THE METRO DADE NOTICE OF ACCEPTANCE
 REPORT #990212.09 IS ILLEGIBLE.
  
 NOA #97-1204.02 IS EXPIRED.
  
 00-0721.05 FOR THE SHUTTERS DOES NOT
 HAVE THE COMPONENTS SELECTED OR THE
 LOCATION OF THEIR PROPOSED APPLICATION
 ON THE BUILDING.SHUTTERS ON
 MULTI-STORY BUILDINGS IN LIEU OF IMPACT
 RESISTANT GLAZING, ARE SUBJECT TO
 APPROVAL BY THE BUILDING OFFICIAL ON A
 CASE BY CASE BASIS.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO THE
 COUNTY FOR THE CITY, THE PERMIT PLANS
 STAMPED BY THAT OFFICE,AND A COPY OF
 THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 561-233-5025 FOR
 MORE INFORMATION.
  
 CONTACT DON NEELY REGARDING THE ONSITE
 THRESHOLD INSPECTOR FOR SPECIFIC CITY
 REQUIREMENTS.561-659-8096 X 8333.