Date |
Text |
2001-11-08 00:00:00 | PLEASE PROVIDE A RECENT PROPERTY SURVEY. |
| |
| THE SOIL REPORT IS REQUIRED TO HAVE THE |
| EMBOSSED SEAL OF THE ENGINEER TOGETHER |
| WITH THE ORIGINAL SIGNATURE AND DATE. |
| THIS IS REQUIRED FOR ALL DOCUMENTS |
| PREPARED BY AN ENGINEER OR ARCHITECT |
| AND SUBMITTED FOR PUBLIC RECORD.SEE |
| FS 471 AND 481 |
| |
| PLEASE PROVIDE THE FIRE DESIGN NUMBERS |
| FOR THE MASONRY WALLS SERVING AS SHAFT |
| ENCLOSURES AND EXTERIOR WALLS.SEE SBC |
| 701.5. |
| |
| WHAT IS THE MEANING OF THE NOTE ON |
| SHEETA0-1 "ADJACENT BUILDING WALL |
| CONSTRUCTED AS FIRE WALL AS DEFINED BY |
| CODE." ? |
| |
| THE DOORS TO THE CLUBHOUSE AND FITNESS |
| ROOMS SHOWN AS #26 ARE REQUIRED TO BE |
| FIRE RATED.SEE SBC 705.1.2 AND |
| 704.1.1. |
| |
| |
| SBC 1008 REQUIRES ONE OF THE EXIT STAIRS |
| TO BE CONTINUOUS TO THE ROOF. |
| |
| SBC 3104.3 REQUIRES "PROTECTION AT THE |
| INTERFACE" WHERE THE COVERED WALKWAY |
| JOINS THE BUILDING. |
| |
| NEITHER THE PLANS NOR THE SPECIFICATIONS |
| INDICATE THE USE OF FIRE RETARDANT |
| TREATED, (FRT) BLOCKING AS PROVIDED FOR |
| IN SBC 609 AND SBC 707.1. |
| |
| SBC 104.2.1 DOES NOT ALLOW CITING THE |
| CODE IN LIEU OF SPECIFIC DESIGN |
| INFORMATION SUCH AS THAT FOUND ON SHEET |
| A-29 "ADHERE DYPLAST W/ STANDARD |
| BUILDING CODE 1403.6.8 ..."WHICH IS |
| NOT A VALID CODE SECTION ANYWAY, PLEASE |
| REVISE AS NECESSARY. |
| |
| DETAIL 1/A12 ON SHEET A29. SHOW A |
| SPECIFIC CONNECTION DETAIL FOR THE |
| STONE CORBEL OR IF DESIGN IS |
| DESIGNATED, THE LOCATION, NATURE, |
| DIRECTION AND MAGNITUDE OF THE FORCES |
| TO BE RESISTED. |
| |
| MOST OF THE PAGES IN THE STRUCTURAL |
| CALCULATIONS DO NOT PERTAIN TO THIS |
| BUILDING.PLEASE PROVIDE COMPLETE |
| CALCULATIONS DEMONSTRATING COMPLIANCE |
| WITH SBC 1601 AND NOT JUST A WIND |
| RESISTANCE INVESTIGATION. |
| |
| SHEET S-1.1 NOTE #8, WHAT IS THE TOP OF |
| FOOTING ELEVATIONS? |
| |
| SEE SBC 1608.2.2 FOR THE GUARDRAIL |
| DESIGN LOADS SHOWN ON SHEET A27 IN |
| DETAIL 5/A25. |
| |
| SHEET S 1-1 DEPICTS COLUMNS NUMBERED 1 |
| THROUGH 48 AND THE COLUMN SCHEDULE ON |
| SHEET S 4-1 LISTS ONLY 42.THERE IS NO |
| DETAIL FOR COLUMN #46. |
| |
| A THRESHOLD INSPECTION PLAN IS REQUIRED |
| FOR THIS BUILDING AS PROVIDED FOR IN FS |
| 553.71. |
| |
| SEVERAL AREAS OF THE SPECIFICATIONS |
| ERRONEOUSLY CITE A 110 MPH WIND SPEED. |
| PLEASE REVISE AS NECESSARY AND INCLUDE |
| A SKETCH OF THE BUILDING DEFINING THE |
| PRESSURE ZONES AND THEIR ATTENDANT |
| PRESSURES. |
| |
| SMOKE DETECTORS ARE NOT SHOWN INSIDE OF |
| THE SLEEPING ROOMS AS PROVIDE FOR IN |
| NFPA 72 WHICH IS INVOKED BY SBC 905.2. |
| |
| THE STAIR SECTIONS SHOWN WITH RISER |
| HEIGHTS OF 6.5" OR LESS WHEN TAKEN |
| TOGETHER WITH THE DECLARED 11" TREAD DO |
| NOT MEET THE 24"- 25" OF SBC 1007.3.1. |
| SEE ALSO NFPA 101 FOR THE 7/11 |
| REQUIREMENT. |
| |
| PLEASE PROVIDE CALCULATIONS AND A |
| WRITTEN NARRATIVE TO BETTER DESCRIBE |
| THE SEQUENCE OF OPERATIONS FOR SMOKE |
| CONTROL DECLARED ON SHEET M-8. |
| DEMONSTRATE THAT THE BAROMETRIC RELIEF |
| DAMPER WILL PROVIDE FOR AT LEAST 2500 |
| CFM FLOWINGAND ANTICPATED STACK |
| PRESSURES IN THE BUILDING.SEE SBC |
| 412.11 (5). |
| |
| DESCRIBE HOW SMOKE REMOVAL FROM THE |
| CORRIDORS WILL BE ACCOMPLISHED AT A |
| RATE OF AT LEAST 6 AIR CHANGES PER |
| HOUR. SEE SBC 412.5 (3) IF THIS IS THE |
| INTENDED METHOD. |
| |
| SHEET E3-5 DOES NOT SHOW THE FIRE |
| DEPARTMENT COMMUNICATION SYSTEM |
| REQUIRED BY SBC 412.3.3.ARE THE MARKS |
| SHOWN ON THE PLANS AS [T] THE INTENDED |
| LOCATIONS? |
| |
| E 3-5, OR THE SPECIFICATIONS, DO NOT |
| SHOW THE BACKUP POWER SUPPLY FOR THE |
| ALARM SYSTEM. ELEVATOR RECALL BY |
| ELEVATOR LOBBY SMOKE DETECTOR IS NOT |
| NOTED IN THE SEQUENCE OF OPERATION. SEE |
| SBC 412.6.3. |
| |
| THERE IS NO SPECIFICATION FOR THE |
| GENERATOR FUEL SUPPLY.SEE SBC |
| 412.7.1.2.ALSO THE E SHEETS DO NOT |
| CLEARLY INDICATE THE MANDATORY STAND BY |
| POWER LOADS TO BE CARRIED BY THE |
| GENERATOR.SEE SBC 412.7.2. |
| |
| SEVERAL OF THE DOORS WITHIN THE UNITS DO |
| NOT MEET THE NOMINAL 32" WIDTH REQUIRED |
| BY THE FAIR HOUSING ACT. TOILET AND |
| POWDER ROOMS, BEDROOMS, WALKIN CLOSETS, |
| PATIOS, AND SIMILAR LIVING AREAS AS |
| CITED IN THAT LAW.PLEASE REVISE AS |
| NECESSARY. |
| |
| THE METRO DADE NOTICE OF ACCEPTANCE |
| REPORT #990212.09 IS ILLEGIBLE. |
| |
| NOA #97-1204.02 IS EXPIRED. |
| |
| 00-0721.05 FOR THE SHUTTERS DOES NOT |
| HAVE THE COMPONENTS SELECTED OR THE |
| LOCATION OF THEIR PROPOSED APPLICATION |
| ON THE BUILDING.SHUTTERS ON |
| MULTI-STORY BUILDINGS IN LIEU OF IMPACT |
| RESISTANT GLAZING, ARE SUBJECT TO |
| APPROVAL BY THE BUILDING OFFICIAL ON A |
| CASE BY CASE BASIS. |
| |
| BEFORE A PERMIT TO CONSTRUCT MAY BE |
| ISSUED, IMPACT FEES MUST BE PAID TO THE |
| COUNTY FOR THE CITY, THE PERMIT PLANS |
| STAMPED BY THAT OFFICE,AND A COPY OF |
| THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION.CALL 561-233-5025 FOR |
| MORE INFORMATION. |
| |
| CONTACT DON NEELY REGARDING THE ONSITE |
| THRESHOLD INSPECTOR FOR SPECIFIC CITY |
| REQUIREMENTS.561-659-8096 X 8333. |