Plan Review Notes For Permit 01091426 |
Permit Number |
01091426 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2002-05-02 00:00:00 | ~~~~~~~~~~~~~~~~~~UNSAT!~~~~~~~~~~~~~~~~ | | | | 1} PLEASE REDRAW THE CHANGES THAT WERE | | MADE IN PENCIL TO MAKE THEM A PERMINENT | | PART OF THE DOCUMENT. | | | | 2} SMOKE DETECTORS ARE REQUIRED | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | ALSO ON EACH LEVEL OF A MULTI-LEVEL | | DWELLING UNIT. ROOMS WITH BATHS AND OR | | CLOSETS ARE CONSIDERED SLEEPING ROOMS. | | PER NFPA-72 2-2.1.1.1. | | IN THE VICINITY OF BEDROOMS AND CLOSE | | PROXIMITY OF STIRWAYS. 2-5.2.1.3 | | 3'FT FROM BATHS/KITCHENS.2-5.2.1.6 | | 3RD FLOOR. | | | | 3} ONE SET OF PLANS HAS NO SEAL ON A5 | | OR A6. | | | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/659-8096 EXT.8392 |
|