Plan Review Notes
Plan Review Notes For Permit 01091426
Permit Number 01091426
Review Stop E
Sequence Number 2
Notes
Date Text
2002-03-14 00:00:00****************** UNSAT **************
  
 PLEASE NOTE THAT NOT ALL NOTES FROM
 FIRST REVIEW WERE ADDRESSED.
  
 1) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 SEE NFPA-72 2-5-2.1.3
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
 PLEASE NOTE, NO PANEL SCHEDULE SUBMITTED
 OR LOAD CALCULATIONS.220-3-C-1/215-5
  
 3) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
 STILL MISSING IN MANY LOCATIONS.
 PLEASE CLARFIY"FIXTURES"? SHOWN ON 3RD
 FLOOR LEVEL. LIGHTS? HOW ARE THEY
 CONTROLLED?
  
 4) PLEASE NOTE MISSING OUTLET(S) REQ`D
 BY 210-52E OF THE NEC.
  
 5) PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.2
 MECHANICAL CODE.
 PLEASE CLARIFY FOR AHU#2 SHOWN ABOVE
 BATH ROOM?
  
 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 7)NOTE: PLEASE NOTE KITCHENCOUNTERTOP
 RECEPT SPACING FOR PENINSULAR.PLEASE
 SEE 210-52-C-3 AND 4.
  
 8) PLEASE NOTE EITHER MISSING EGRESS
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210-70 OF THE NEC.
 MISSING IN BOTH SMALL BATHS DOWNSTAIRS.
 PLEASE NOTE GFI IN SM.BATH 210-8.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372