Plan Review Notes
Plan Review Notes For Permit 01091426
Permit Number 01091426
Review Stop B
Sequence Number 2
Notes
Date Text
2002-04-03 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01091425
 222 GREGORY RD
 CONT: MEN AT WORK
 TEL: 585-9152
 CEL: 707-6967
  
 SBC= 1997 STANDARD BUILDING CODE
  
 1) PRODUCT APPROVAL REPORT99-0128.01
 IS FOR OUTSWING ALUMINIUM FRENCH DOORS.
 A SINGLE OR PAIR OF DOORS ONLY! PRODUCT
 LIMITATIONS 3.1 STATES THAT IT IS FOR
 A SINGLE DOOR OR PAIR OF DOORS ONLY, THE
 PRODUCT DESCRIPTION ALSO REFLECTS STRICT
 COMPLIANCE WITH TECH DRAWINGS # 971.
 UNLESS A STRUCTURAL MEMBER IS INTRODUCED
 BETWEEN THE PAIR OF DOORS AND SIDE LITES
 SEPERATING THE 2 ELEMENTS THIS REPORT
 SHALL NOT BE USED FOR THIS APPLICATION.
 IF A STRUCTURAL MEMBER IS USED TO SEPERA
 TE THE 2 ELEMENTS A REPORT SHALL BE REQU
 IRED FOR THE SIDELITE ELEMENTIF IT EX-
 CEEDS THE LIMITAATION FOR REPORT#
 99-0218.01 ALREADY SUPPLIED. NOTE SIDE
 LIGHT SHALL BE TEMPERED GLASS!
 2) TRUSS ENGINEERING: THE DESIGN CERTI-
 FICATION SHEET INDICATES A MEAN ROOF
 HEIGTH OF 29'-3", THE TRUSS ENGINEERING
 SHEETS INDICATE MULTIPLE HEIGTHS!!!!!
 SBC 1606.2.2.1 WIND PRESSURE MIXING OF
 COEFFICIENTS & DYNAMIC PRESSURES FROM
 DIFFERENT SOURCES SHALL NOT BE PERMITTED
 A SINGLE MEAN ROOF HEIGTH IS TO BE USED
 FOR THE ENTIRE STRUCTURE, NOT THE
 VARIOUS MEAN ROOF HEIGTH OF THE VARIOUS
 TRUSSES. TRUSS ENGINEERING TO BE CALCULA
 TED WITH THE WORST CASE MEAN ROOF HEIGTH
 3) DISCREPANCY BETWEEN A-4,A-7 & THE
 TRUSS ENGINEERING LAYOUT SHEET. CABANA
 ROOM, SHEET A-4 & THE TRUSS LAY OUT
 SHEET FROM A-1 INDICATE A WALL BELOW THE
 TRUSS ALONG THE BACK WALL. A-7 INDICATES
 THE USE OF A GIRDER TRUSS. SINCE A-7 IS
 DESIGNED FROM THE ARCH HE IS NOT SPECIF-
 FYING THE CONNECTION THINKING TRUSS/
 GIRDER CONNECTIION WHICH IS SPECED FROM
 THE TRUSS ENG. THE TRUSS ENG LAYOUT
 SHEET THIS WALL SHOWS UP AS A WALL, THE
 TRUSS ENGINEER NOT SPECIFYING THE CONNEC
 TION TRUSS TO BEAM!!!
 BOTTOM LINE NO ANCHOR IS DETAILED.
 4) TRUSS ENG CUT SHEETS WG1 THREE MEMBER
 GIRDER NEEDS ATTENTION?TRUSS ENG SHEET
 INDICATES A UPLIFT VALUE OF 15,167 LBS
 AND A REACTION VALUE OF 24,614 / 32"=
 769 LBS / INCH.*****EXCEEDS CRUSHING
 VALUES*****
 5) CONTRACTOR TO SUBMIT PLANS TO PALM
 BEACH COUNTY FOR IMPACT FEE ASSESSMENT!
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X 8412