2001-10-19 00:00:00 | ***************** UNSAT ************** |
| |
| 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW EQUIPMENT BEING INSTALLED. |
| MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| THE AVAILABLE FAULT CURRENT PER 110-9. |
| |
| 2) NOTE: PLEASE SHOW ALL OUTLETS SERVING |
| KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| -ED PER 210-8-A-6. |
| |
| 3) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| CIRCUIT(S) PER 210-11-C-3. |
| MUST BE 20A AND #12AWG. |
| |
| 4) NOTE: PLEASE SHOW ALL OUTLET SPACING |
| TO MEET 2`,6`,12` RULE PER 210-52. |
| |
| 5) PLEASE NOTE MISSING OUTLET(S) REQ`D |
| BY 210-52E OF THE NEC. |
| |
| |
| 6) PLEASE NOTE MISSING OUTLET FOR A/C |
| EQUIPMENT PER 210-63 OF NEC AND 309.2 |
| MECHANICAL CODE. |
| |
| 7) NOTE: SMOKE DETECTORS ARE REQUIRED |
| INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| DWELLING UNIT. ROOMS WITH BATHS AND OR |
| CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| PER NFPA-72 2-2.1.1.1. |
| |
| 8)NOTE: PLEASE NOTE MISSING OUTLET FOR |
| HALLWAY(S) 210-52H |
| |
| 9)NOTE: PLEASE NOTE MISSING DISCONNECT |
| FORA/C CU 440-11 |
| |
| 10)NOTE: PLEASE SHOW ALL BATHS AS GFI/ |
| GFI PROTECTED. 210-8 |
| |
| 11)NOTE: PLEASE NOTE MISSING OUTLET FOR |
| BATH(S) PER 210-52D |
| |
| 12)NOTE: PLEASE NOTE MISSING OUTLETS |
| FOR KITCHEN COUNTERSPACE PER 210-52-C-3 |
| |
| 13)NOTE: PLEASE NOTE MISSING MEANS OF |
| EGRESS LIGHTING FOR STAIRS? 210-70 |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-659-8096 EXT 8372 |