Plan Review Notes
Plan Review Notes For Permit 01091426
Permit Number 01091426
Review Stop E
Sequence Number 1
Notes
Date Text
2001-10-19 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
  
 3) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 4) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
  
 5) PLEASE NOTE MISSING OUTLET(S) REQ`D
 BY 210-52E OF THE NEC.
  
  
 6) PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.2
 MECHANICAL CODE.
  
 7) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 8)NOTE: PLEASE NOTE MISSING OUTLET FOR
 HALLWAY(S) 210-52H
  
 9)NOTE: PLEASE NOTE MISSING DISCONNECT
 FORA/C CU 440-11
  
 10)NOTE: PLEASE SHOW ALL BATHS AS GFI/
 GFI PROTECTED. 210-8
  
 11)NOTE: PLEASE NOTE MISSING OUTLET FOR
 BATH(S) PER 210-52D
  
 12)NOTE: PLEASE NOTE MISSING OUTLETS
 FOR KITCHEN COUNTERSPACE PER 210-52-C-3
  
 13)NOTE: PLEASE NOTE MISSING MEANS OF
 EGRESS LIGHTING FOR STAIRS? 210-70
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372