2001-10-29 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT # 01091425 |
| 222 GREGORY RD |
| CONT: MEN AT WORK CONST |
| TEL: 585-9152 |
| CELL: 707-6967 |
| |
| SBC= 1997 STANDARD BUILDING CODE |
| SBC*= AMENDMENTS/ STANDARD BUILDING CODE |
| |
| 1)- PRODUCT APPROVAL 99-0128.01: |
| SWD-101 OUTSWING FRENCH DOORS 3.0 LIMIT- |
| TATIONS, SINGLE UNIT, OR PAIR OF DOORS, |
| REPORT NOT TESTED WITH SIDELITES! SEE |
| GREAT ROOM. |
| |
| 2)- PRODUCT APPROVAL, WINDOWS: MISSING |
| MULLION REPORT FOR WINDOWS. |
| |
| 3)- SSHEET A-1: |
| A) MISSING COLUMN INFORMATION, ACI |
| 530-95 LATERAL TIES 5.9.1.6. |
| B) SBC 104.2.2* THE PLANS INDICATE A |
| COMBINATION OF POURED COLUMNS & BEAMS |
| HOOPS VS. GROUTED MASONARY & BOND |
| BEAMS, WHICH IS TO BE USED? PUMP MIX |
| OR GROUT? WHAT STRENGTH? |
| C) INFO FOR THE SPIRAL STAIRS? |
| D) LOFT: INDICATE THE LANDINGS FOR THE |
| 2ND 3RD FLOOR. |
| E) LOFT: SEPERATION OF LOFT & OPEN AREA |
| WALL OR GAURDRAIL? |
| |
| 4)- SHEET A-2 INDICATES A 2ND & 3RD |
| FLOOR, SBC TABLE 600 TYPE VI-1 HR |
| PROTECTED, OR TYPE VI UNPROTECTED/ |
| SPRINKLERED ( FOOTNOTE H) GIVES ALLOW |
| ANCES FOR A 3RD FLOOR (SPRINKLERED). |
| GIVE THE FLOOR CEILING 1 HR RATING |
| ASSEMBLIES OR SUPPLY THE FIRE SPRINK- |
| LER PLANS. |
| |
| 5)- SHEET A-3 |
| A) FIRST FL ELEVATION INDICATES A 12' |
| X 6' WINDOW, IS THERE A BEAM AS |
| DIPICTED? |
| B) 2ND / 3RD FLOOR MISSING HEADER INFOR |
| MATION, SBC 2308.3.1. HEADERS2308.3.2 |
| THE NUMBER OF JACK STUDS REQUIRED, |
| AND THE TYPE OF CONNECTOR REQUIRED |
| FOR UPLIFT? |
| C) BALCONY; MISSING FLASHING DETAIL FOR |
| THE LIGHTWEIGHT CONCRETE? |
| D) DETAIL FOR THE ANCHORING OF GAURD- |
| RAIL. |
| E) MISSING INFORMATION, 2X12 THE STRAP- |
| PING FOR THTE TOP PLATE AND FLOOR |
| JOIST? |
| |
| 6)- SHEET A-4: |
| A) DISCREPANCY: THE PLANS INDICATE A |
| HAND FRAMED VAULT VS TRUSS LAYOUT |
| T-10. |
| B) DISCREPANCY: CUT SECTIONS A/B ARE |
| FLIPPED. |
| C) SBC 104.2.2. HURRICANE ANCHOR SCHED- |
| ULE, SHOW LOCATION, DIRECTION, & |
| MAGNITUDE OF THE LOADS TO BE RESIST- |
| ED. |
| D) THE DESIGN CERTIFICATION SHEET INDI- |
| CATES A HEIGTH OF 29'-3" VS TRUSS |
| ENGINEERING MULT HEIGTHS. |
| SBC 1606.2.2.1 WIND PRESSURE MIXING |
| OF COEFFICIENTS & DYNAMIC PRESSURES |
| FROM DIFFERENT SCOURCES SHALL NOT |
| BE PERMITTED. |
| E) SEC A BUILT UP GIRDER INDICATE TYPE |
| OF ANCHORS TO BE SUPPLIED FOR |
| UPLIFT & REACTION. *** REACTION |
| 24,614LBS @ 33 SQ IN = 745 LBS/ IN. |
| EXCEEDS CRUSHING VALUES |
| F) WALL SECTION "B" IS MISSING THE |
| FIRE STOPPING 2305.1.4(5) |
| G) GREAT ROOM- DETAIL FOR GABLE ENDS |
| HOW WILL END WALLS TIE IN? DIAPHRAM? |
| |
| 7)- PLEASE PROVIDE A ROOF NAILING |
| SCHEDULE AS PER SBC 2306.1*. |
| |
| PLANS ARE INCOMPLETE ENOUGH TO DO A |
| THROUGH PLAN REVIW |
| BUILDING PLAN REVIW |
| JIM WITMER |
| (561) 659-8096 X 8412 |