2001-10-29 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01091425
 222 GREGORY RD
 CONT: MEN AT WORK CONST
 TEL: 585-9152
 CELL: 707-6967
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS/ STANDARD BUILDING CODE
  
 1)- PRODUCT APPROVAL 99-0128.01:
 SWD-101 OUTSWING FRENCH DOORS 3.0 LIMIT-
 TATIONS, SINGLE UNIT, OR PAIR OF DOORS,
 REPORT NOT TESTED WITH SIDELITES! SEE
 GREAT ROOM.
  
 2)- PRODUCT APPROVAL, WINDOWS: MISSING
 MULLION REPORT FOR WINDOWS.
  
 3)- SSHEET A-1:
 A) MISSING COLUMN INFORMATION, ACI
 530-95 LATERAL TIES 5.9.1.6.
 B) SBC 104.2.2* THE PLANS INDICATE A
 COMBINATION OF POURED COLUMNS & BEAMS
 HOOPS VS. GROUTED MASONARY & BOND
 BEAMS, WHICH IS TO BE USED? PUMP MIX
 OR GROUT? WHAT STRENGTH?
 C) INFO FOR THE SPIRAL STAIRS?
 D) LOFT: INDICATE THE LANDINGS FOR THE
 2ND 3RD FLOOR.
 E) LOFT: SEPERATION OF LOFT & OPEN AREA
 WALL OR GAURDRAIL?
  
 4)- SHEET A-2 INDICATES A 2ND & 3RD
 FLOOR, SBC TABLE 600 TYPE VI-1 HR
 PROTECTED, OR TYPE VI UNPROTECTED/
 SPRINKLERED ( FOOTNOTE H) GIVES ALLOW
 ANCES FOR A 3RD FLOOR (SPRINKLERED).
 GIVE THE FLOOR CEILING 1 HR RATING
 ASSEMBLIES OR SUPPLY THE FIRE SPRINK-
 LER PLANS.
  
 5)- SHEET A-3
 A) FIRST FL ELEVATION INDICATES A 12'
 X 6' WINDOW, IS THERE A BEAM AS
 DIPICTED?
 B) 2ND / 3RD FLOOR MISSING HEADER INFOR
 MATION, SBC 2308.3.1. HEADERS2308.3.2
 THE NUMBER OF JACK STUDS REQUIRED,
 AND THE TYPE OF CONNECTOR REQUIRED
 FOR UPLIFT?
 C) BALCONY; MISSING FLASHING DETAIL FOR
 THE LIGHTWEIGHT CONCRETE?
 D) DETAIL FOR THE ANCHORING OF GAURD-
 RAIL.
 E) MISSING INFORMATION, 2X12 THE STRAP-
 PING FOR THTE TOP PLATE AND FLOOR
 JOIST?
  
 6)- SHEET A-4:
 A) DISCREPANCY: THE PLANS INDICATE A
 HAND FRAMED VAULT VS TRUSS LAYOUT
 T-10.
 B) DISCREPANCY: CUT SECTIONS A/B ARE
 FLIPPED.
 C) SBC 104.2.2. HURRICANE ANCHOR SCHED-
 ULE, SHOW LOCATION, DIRECTION, &
 MAGNITUDE OF THE LOADS TO BE RESIST-
 ED.
 D) THE DESIGN CERTIFICATION SHEET INDI-
 CATES A HEIGTH OF 29'-3" VS TRUSS
 ENGINEERING MULT HEIGTHS.
 SBC 1606.2.2.1 WIND PRESSURE MIXING
 OF COEFFICIENTS & DYNAMIC PRESSURES
 FROM DIFFERENT SCOURCES SHALL NOT
 BE PERMITTED.
 E) SEC A BUILT UP GIRDER INDICATE TYPE
 OF ANCHORS TO BE SUPPLIED FOR
 UPLIFT & REACTION. *** REACTION
 24,614LBS @ 33 SQ IN = 745 LBS/ IN.
 EXCEEDS CRUSHING VALUES
 F) WALL SECTION "B" IS MISSING THE
 FIRE STOPPING 2305.1.4(5)
 G) GREAT ROOM- DETAIL FOR GABLE ENDS
 HOW WILL END WALLS TIE IN? DIAPHRAM?
  
 7)- PLEASE PROVIDE A ROOF NAILING
 SCHEDULE AS PER SBC 2306.1*.
  
 PLANS ARE INCOMPLETE ENOUGH TO DO A
 THROUGH PLAN REVIW
 BUILDING PLAN REVIW
 JIM WITMER
 (561) 659-8096 X 8412