Date |
Text |
2001-11-06 00:00:00 | CHECKLIST: |
| 1-SEE COMMENTS BY PLUMBING. REVISE |
| ORIGINAL DRAWINGS TO AVOID DELAYS AND |
| ADDITIONAL FEES. |
| 2-NEED TO RECORD NOTICE OF COMMENCEMENT. |
| 3-NEED ADDITIONAL SOIL BORINGS FOR EACH |
| STRUCTURE AS RECOMMENDED ON THE PRE- |
| LIMINARY SOIL TEST REPORT. |
| 4-PROVIDE PRODUCT APPROVAL FOR: |
| A)GARAGE DOORS PRODUCT APPROVAL WAS |
| DELETED FROM SBCCI LISTING. |
| B)WINDOW MULLIONS. |
| 5-CLEARLY INDICATE ON PLANS OPTIONS TO |
| BE BUILT AND PROVIDE PRODUCT APPROVALS |
| OR CROSS OUT THE OPTIONS. |
| 6-OWES ADDITIONAL FEES FOR UPDATED VALUE |
| AND RADON FEES. PLEASE PAY ATTACHED |
| RECEIPTS AND BRING PAID RECEIPTS. |
| 7-PROVIDE CERTIFICATION FOR TWO HR FIRE |
| RATED CONCRETE BLOCK THAT COMPLIES W/ |
| SECTION 709.3 SBC 1997. |
| |
| NOTE: |
| THIS CERTIFICATION IS GIVEN BY THE |
| MANUFACTURER ACCORDING TO THE CONCRETE |
| BLOCK EQUIVALENT THICKNESS AND TYPE |
| OF AGGREGATES USED. |
| 8-PROVIDE COMPLETE INFORMATION FOR STORM |
| PANELS OR APPLY FOR A SEPARATE PERMIT. |
| |
| |
| NOTES: |
| -DRAWINGS AND COMMENTS TO BE FILED UNDER |
| PERMIT # 01091398. |
| -THESE COMMENTS APPLY TO PERMIT #S: |
| 01091398, 01091400, 01091403 AND |
| 01091405. |