Plan Review Notes For Permit 01091396 |
Permit Number |
01091396 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-10-12 00:00:00 | DENIED | | REFERENCE: SPC-94 - FACBC-97 | | | | 1) PAGE PO.1 PLUMBING NOTES #13 & #18. | | AIR CHAMBERS DO NOT WORK AND SHOULD NOT | | BE USED. IF THEY ARE USED THEY SHALL | | COMPLY WITH SPC-94 SEC 607.8.3 AND BE | | ACCESSIBLE AND RECHARGABLE PER WH-PDI | | 201. WATER HAMMER ARRESTORS SHALL BE | | SIZED AND LOCATED PER MANUFACTURE IN- | | STALLATION INSTRUCTIONS AND WH-PDI 201. | | THEY SHALL BE LOCATED CLOSE TO THE | | SOURCE AND NOT AT TOP OF DROP AS SHOWN. | | | | 2) OCCUPANT CONTENT PER SHIFT REQUIRED | | FOR WAREHOUSE AREA, SUBSTANTIATED BY | | OWNER PER SPC-94 TABLE 407 TO CALCULATE | | MINIMUM FACILITIES. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT. 8377 |
|