Plan Review Notes
Plan Review Notes For Permit 01091396
Permit Number 01091396
Review Stop P
Sequence Number 1
Notes
Date Text
2001-10-12 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) PAGE PO.1 PLUMBING NOTES #13 & #18.
 AIR CHAMBERS DO NOT WORK AND SHOULD NOT
 BE USED. IF THEY ARE USED THEY SHALL
 COMPLY WITH SPC-94 SEC 607.8.3 AND BE
 ACCESSIBLE AND RECHARGABLE PER WH-PDI
 201. WATER HAMMER ARRESTORS SHALL BE
 SIZED AND LOCATED PER MANUFACTURE IN-
 STALLATION INSTRUCTIONS AND WH-PDI 201.
 THEY SHALL BE LOCATED CLOSE TO THE
 SOURCE AND NOT AT TOP OF DROP AS SHOWN.
  
 2) OCCUPANT CONTENT PER SHIFT REQUIRED
 FOR WAREHOUSE AREA, SUBSTANTIATED BY
 OWNER PER SPC-94 TABLE 407 TO CALCULATE
 MINIMUM FACILITIES.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377