Plan Review Notes
Plan Review Notes For Permit 01091396
Permit Number 01091396
Review Stop E
Sequence Number 1
Notes
Date Text
2001-10-01 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT GROUNDING FOR
 TRANSFORMER NEEDS TO BE SHOWN TO EXIST-
 -ING BLDG STEEL 250-30. PLEASE NOTE THAT
 IT IS NOT KNOWN IF THERE ARE ANY BREAKS
 OF PVC IN THE COLD WATER LINE.
  
 2)NOTE: PLEASE SHOW LOAD CALCULATIONS,
 AND ALL CONTINUOUS LOADS AT 125%.
 215-5,230-42,215-2-3.
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PLEASES NOTE THAT AIC RATINGS ARE
 SHOWN FOR PANELS BUT NOT MIAN DISCONNECT
 PLEASE SHOW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372