2001-10-10 00:00:00 | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | FOR REVIEW. | | | | 1.EXISTING DUCTWORK - WHAT SIZE, IS | | THIS DUCTWORK BEING TIED INTO NEW | | 5 TON SYSTEM?WHAT WAS THE SIZE OF | | THE OLD SYSTEM. | | | | 2.LOCATION OF THE 5 TON SYSTEM, IF | | INSTALLED IN THE ATTIC SHALL HAVE | | AN ACCESS OPENING NO LESS THAN 22" | | X 36" CONTINUOUS FROM OPENING TO THE | | EQUIPMENT.SHALL HAVE AN ACCESSIBLE | | DISCONNECT SWITCH, A 110-120 VOLT | | A/C GROUNDING TYPE CONVENIENCE OUT- | | LET AND A LIGHT ON THE SERVICE SIDE | | OF THE EQUIPMENT CONTROLLED BY A | | SWITCH AT THE ACCESS OPENING. | | | | 3.AXUILIARY DRAIN PAN WITH OVERFLOW | | PROTECTION BY MEANS OF A FLOAT | | SWITCH OR SEPARATE DRAIN TERMINATING | | AT CONSPICUOUS POINT TO SERVE AS AN | | ALARM THAT THE REGULAR DRAIN IS | | RESTRICTED. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|