Plan Review Notes
Plan Review Notes For Permit 01091365
Permit Number 01091365
Review Stop E
Sequence Number 1
Notes
Date Text
2001-10-09 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT NO LOAD CALCS/
 PANEL SCHEDULES/ RISER DIAGRAMS ETC
 WERE SUBMITTED? 220-3-C1/215-5 310-16,,
 ,,,
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 3) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 4) PLEASE NOTE EITHER MISSING EGRESS
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210-70 OF THE NEC.
 PLEASE SHOW SWITCHING OF EGRESS LIGHTING
 FOR STAIRWAY.?
 ELECTRICAL PLANS NEED TO SHOW STAIRS
  
 5)NOTE: PLEASE SHOW SINKL LOCATIONS FOR
 BATHS SO OUTLET LOCATIONS MEET 210-52D
  
 6)NOTE: PLEASE NOTE DEDICATED
 ELECTRICALSPACE FOR PANEL SHOWN IN
 STORAGE ROOM
 IN A SF RESIDENCE. ALSO SEE 384-7
 IGNITIBLE MATERIALS.
  
 7) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
 CLARIFY SPACING IN "NEW GUEST BR"
 ALSO EGRESS LIGHTING? 210-70
  
 8)NOTE: PLEASE NOTE MISSING NEW CU FOR
 A/C ON ELECTRICAL PLAN WITH DISCONNECTS
 PER 440-11
  
 9) PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.1
 MECHANICAL CODE.
  
 10)NOTE: PLEASE NOTE EGRESS FROM BATH
 TO OUTSIDE W/ NO EGRESS LIGHTING
 CONTROL-S? 210-70
  
 11)NOTE: PLEASE NOTE CIRCUITS BEING
 SHOWN FOR DRYER AND WATER HEATER IN
 LAUNDRY ROOM BUT NOT FOR WASHER? PER
 210-52-F. PLEASE CLARFIY-EXISTING IN
 OTHER LOCATION?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372