2001-10-09 00:00:00 | *************** UNSAT **************** |
| |
| 1)NOTE: PLEASE NOTE THAT NO LOAD CALCS/ |
| PANEL SCHEDULES/ RISER DIAGRAMS ETC |
| WERE SUBMITTED? 220-3-C1/215-5 310-16,, |
| ,,, |
| |
| 2) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| CIRCUIT(S) PER 210-11-C-3. |
| MUST BE 20A AND #12AWG. |
| |
| 3) NOTE: SMOKE DETECTORS ARE REQUIRED |
| INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| DWELLING UNIT. ROOMS WITH BATHS AND OR |
| CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| PER NFPA-72 2-2.1.1.1. |
| |
| 4) PLEASE NOTE EITHER MISSING EGRESS |
| LIGHTING AND/OR CLARIFY EGRESS LIGHTING |
| PER 210-70 OF THE NEC. |
| PLEASE SHOW SWITCHING OF EGRESS LIGHTING |
| FOR STAIRWAY.? |
| ELECTRICAL PLANS NEED TO SHOW STAIRS |
| |
| 5)NOTE: PLEASE SHOW SINKL LOCATIONS FOR |
| BATHS SO OUTLET LOCATIONS MEET 210-52D |
| |
| 6)NOTE: PLEASE NOTE DEDICATED |
| ELECTRICALSPACE FOR PANEL SHOWN IN |
| STORAGE ROOM |
| IN A SF RESIDENCE. ALSO SEE 384-7 |
| IGNITIBLE MATERIALS. |
| |
| 7) NOTE: PLEASE SHOW ALL OUTLET SPACING |
| TO MEET 2`,6`,12` RULE PER 210-52. |
| CLARIFY SPACING IN "NEW GUEST BR" |
| ALSO EGRESS LIGHTING? 210-70 |
| |
| 8)NOTE: PLEASE NOTE MISSING NEW CU FOR |
| A/C ON ELECTRICAL PLAN WITH DISCONNECTS |
| PER 440-11 |
| |
| 9) PLEASE NOTE MISSING OUTLET FOR A/C |
| EQUIPMENT PER 210-63 OF NEC AND 309.1 |
| MECHANICAL CODE. |
| |
| 10)NOTE: PLEASE NOTE EGRESS FROM BATH |
| TO OUTSIDE W/ NO EGRESS LIGHTING |
| CONTROL-S? 210-70 |
| |
| 11)NOTE: PLEASE NOTE CIRCUITS BEING |
| SHOWN FOR DRYER AND WATER HEATER IN |
| LAUNDRY ROOM BUT NOT FOR WASHER? PER |
| 210-52-F. PLEASE CLARFIY-EXISTING IN |
| OTHER LOCATION? |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-659-8096 EXT 8372 |