2001-10-18 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT # 01091365 |
| 300 34TH ST |
| CONT: WAYNE HETZEL BUILDING |
| PHONE: (561) 881-2108 |
| |
| SBC= 1997 STANDARD BUILDING CODE |
| SBC*= AMENDMENTS TO STANDARD BUILDING |
| CODE |
| 1)- SBC 1606.2.6.2 COMPONENTS & CLADDING |
| A)- WINDOWS INDICATE WHICH KDI WINDOW |
| SYSTEM THAT YOU ARE USING? ONLY THE |
| KDI 2000 WINDOW SYSTEM IS TESTED |
| FOR LARGE MISSLE IMPACT TESTING! |
| IF A KDI WINDOW SYSTEM OTHER THAN |
| THE "2000" SERIESIS INSTALLED, |
| STORM SHUTTERS WILL BE REQUIRED. |
| B)- OUT SWING FRENCH DOORS; WILL RE- |
| QUIRE STORM SHUTTERS. |
| C)- IN SWING FRENCH DOORS; NEW REPORT |
| REQUIRED, EXPIRED |
| D)- SKYLIGHT: MISSING PRODUCT APPROVAL |
| REPORT, GLAZED OPENING WILL REQUIRE |
| LARGE MISSLE IMPACT RESISTANCE TEST |
| ING OR STORM SHUTTERS. |
| E)- STORM SHUTTERS: A KEY DIAGRAPM & |
| INSTALLATION SCHEDULE IS ALSO RE- |
| QUIRED, A SAMPLE IS ATTACHED. |
| |
| 2)- STAIRS: WINDERS, SBC 1007.8.1. |
| A MINIMUM TREAD DEPTH OF 6" AT THE |
| NARROW EDGE & SHALL HAVE A MINIMUM |
| TREAD DEPTH OF 11" AT A POINT 12" |
| FROM THE NARROW EDGE. |
| |
| 3)-SHEET A511 (DETAIL 1) : |
| A)- CEILING LINE/ TRUSS LINE MISSING |
| FIRE BLOCKING |
| B)- 2ND FLOOR WOOD NAILER AT BEAM, |
| REQUIRED TO BE PRESSURE TREATED |
| |
| 4)- SHEET A511 (DETAIL 3) : |
| A)- CAANTILEVERED BALCANY- THE BEAM IN- |
| DICATES THE SIZE OF THE STEEL, BUT |
| NOT THE SIZE OR FREQUENCY OF HOOPS & |
| STIRRUPS. |
| B)- GAURDRAIL TO COMPLY WITH 1015.3, |
| OPENINGS 4" |
| C)- MISSING FIRE STOPPING CEILING LEVEL |
| |
| BUILDING PLAN REVIEW |