2001-10-18 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01091365
 300 34TH ST
 CONT: WAYNE HETZEL BUILDING
 PHONE: (561) 881-2108
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS TO STANDARD BUILDING
 CODE
 1)- SBC 1606.2.6.2 COMPONENTS & CLADDING
 A)- WINDOWS INDICATE WHICH KDI WINDOW
 SYSTEM THAT YOU ARE USING? ONLY THE
 KDI 2000 WINDOW SYSTEM IS TESTED
 FOR LARGE MISSLE IMPACT TESTING!
 IF A KDI WINDOW SYSTEM OTHER THAN
 THE "2000" SERIESIS INSTALLED,
 STORM SHUTTERS WILL BE REQUIRED.
 B)- OUT SWING FRENCH DOORS; WILL RE-
 QUIRE STORM SHUTTERS.
 C)- IN SWING FRENCH DOORS; NEW REPORT
 REQUIRED, EXPIRED
 D)- SKYLIGHT: MISSING PRODUCT APPROVAL
 REPORT, GLAZED OPENING WILL REQUIRE
 LARGE MISSLE IMPACT RESISTANCE TEST
 ING OR STORM SHUTTERS.
 E)- STORM SHUTTERS: A KEY DIAGRAPM &
 INSTALLATION SCHEDULE IS ALSO RE-
 QUIRED, A SAMPLE IS ATTACHED.
  
 2)- STAIRS: WINDERS, SBC 1007.8.1.
 A MINIMUM TREAD DEPTH OF 6" AT THE
 NARROW EDGE & SHALL HAVE A MINIMUM
 TREAD DEPTH OF 11" AT A POINT 12"
 FROM THE NARROW EDGE.
  
 3)-SHEET A511 (DETAIL 1) :
 A)- CEILING LINE/ TRUSS LINE MISSING
 FIRE BLOCKING
 B)- 2ND FLOOR WOOD NAILER AT BEAM,
 REQUIRED TO BE PRESSURE TREATED
  
 4)- SHEET A511 (DETAIL 3) :
 A)- CAANTILEVERED BALCANY- THE BEAM IN-
 DICATES THE SIZE OF THE STEEL, BUT
 NOT THE SIZE OR FREQUENCY OF HOOPS &
 STIRRUPS.
 B)- GAURDRAIL TO COMPLY WITH 1015.3,
 OPENINGS 4"
 C)- MISSING FIRE STOPPING CEILING LEVEL
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096X 8412