Plan Review Notes For Permit 01091304 |
Permit Number |
01091304 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-10-17 00:00:00 | DENIED; | | 1.PAGE 1A & 2 GENERAL NOTES. CHANGE TO | | READ FHA 98 DESIGN MANUAL. | | 2.MODEL 1527 L & R.M/B SHOWS 1'7" TO | | CENTER OF W/C AND IT SHOULD BE 1' 6" | | ALSO SHOW CLEAR FLOOR SPACE FOR LAV. | | PAGE 1A &1B. | | 3.IN BATH 2 SHOW CLEAR FLOOR SPACE FOR | | W/C AND LAV. PAGE 1A &1B. | | 4.MODEL 1409 M/B SHOWS 1'7" TO CENTER | | OF W/C AND IT SHOULD BE 1'6" ALSO | | SHOW CLEAR FLOOR SPACE FOR W/C AND | | LAV. PAGE 1A &1B. | | 5.BATH 2 SHOWS 2'8" OPENING FOR W/C | | 2'9" MIN. SPACE REQUIRED FOR W/C ALSO | | SHOW CLEAR FLOOR SPACE FOR W/C AND LAV | | PAGE 1A &1B. | | 6.PAGE 2 RISER DIAGRAMS. MODEL 1527 & | | 1409. SHOW VENT FOR OPT. L.T. |
|