Plan Review Notes For Permit 01091304 |
Permit Number |
01091304 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-10-27 00:00:00 | CHECKLIST: | | 1-SEE COMMENTS BY PLUMBING. REVISE | | ORIGINAL DRAWINGS TO AVOID DELAYS. | | 2-NEED TO RECORD NOTICE OF COMMENCEMENT. | | 3-NEED ADDITIONAL SOIL BORINGS FOR EACH | | STRUCTURE AS RECOMMENDED ON THE PRE- | | LIMINARY SOIL TEST REPORT. | | 4-PROVIDE PRODUCT APPROVAL FOR: | | A)GARAGE DOORS PRODUCT APPROVAL WAS | | DELETED FROM SBCCI LISTING. | | B)WINDOW MULLIONS. | | | | 5-CLEARLY INDICATE ON PLANS OPTIONS TO | | BE BUILT AND PROVIDE PRODUCT APPROVALS | | OR CROSS OUT OPTIONS. | | 6-OWES ADDITIONAL FEES FOR UPDATED VALUE | | AND RADON FEES. PLEASE PAY ATTACHED | | RECEIPTS AND BRING PAID RECEIPTS. | | 7-PROVIDE CERTIFICATION FOR TWO HR FIRE | | RATED CONCRETE BLOCK THAT COMPLIES W/ | | SECTION 709.3 SBC 1997 ACCORDING TO | | THE EQUIVALENT THICKNESS. | | 8-PROVIDE COMPLETE INFORMATION FOR STORM | | PANELS OR APPLY FOR A SEPARATE PERMIT. | | | | | | | | | | NOTES: | | -DRAWINGS AND COMMENTS TO BE FILED UNDER | | PERMIT #01091304. | | -THESE COMMENTS APPLY TO PERMIT #S: | | 01091304, 01091306, 01091308, 01091312, | | 01091314 AND 01091316. |
|