Plan Review Notes
Plan Review Notes For Permit 01091250
Permit Number 01091250
Review Stop E
Sequence Number 2
Notes
Date Text
2001-10-23 00:00:00******************UNSAT **************
  
 PLEASE NOTE THAT PLANS ARE BEING DENIED
 DUE TO THE REQ`MENTS FOR CHANGE OF USE
 TO COMMERCIAL 104.1.1. SEE COMMENTS
 FROMBLDG OFFICIAL.
  
 PLEASE NOTE THE FOLLOWING MINOR
 ELECTRICAL CHANGES NEEDED.
  
 1)NOTE: PLEASE NOTE ONE ROOM/OFFICE MISS
 ING OUTLETS?
  
 2)NOTE: PLEASE NOTE ALL CONTINOUS LOADS
 INCLUDING LIGHTING TO BE SHOWN AT 125%.
  
  
 PLEASE SUBMIT THESE MINOR CHANGES WHEN
 ALL OF THE OTHER ISSUES WITH ZONING,
 BLDG, PLUMB ETC ARE ADDRESSED.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372