Plan Review Notes For Permit 01091250 |
Permit Number |
01091250 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-10-03 00:00:00 | ************** UNSAT **************** | | | | 1)NOTE: PLEASE NOTE THAT PLANS WERE | | SUBMITTED CHANGING FROM RESIDENTIAL TO | | COMMERCIAL, PLEASE NOTE THAT LOAD | | CALCULATIONS NEED TO BE SHOWN FOR A | | OFFICE AND CONTINUOUS LOADS NEED TO BE | | SHOWN AT 125%. OUTLETS AT 180VA.EACH | | | | 2)NOTE: PLEASE SHOW LOCATION OF PANEL | | ON FLOOR LAYOUT. | | | | 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 4)NOTE: PLEASE CLARIFY ANY COLD WATER | | AS PART OF GROUNDING ELECTRODE SYSTEM. | | 250-50 | | | | 5)NOTE: PLEASE SHOW A/C LOCATIONS ON | | PLANS AND DISCONNECTS PER 440-11. | | | | 6)NOTE: PLEASE SHOW WATER HEATER | | LOCATION. | | | | 7)NOTE: PLEASE NOTE REQ`D EXITS LIGHTS | | AND EMERGENCY LIGHTS. | | ART 700 | | | | PLEASE NOTE THAT IF HOUSE IS GOING TO | | REMAIN AS RESIDENTIAL THEN PLANS WOULD | | NEED TO REFLECT A SFR. W/ SD`S, KITCHEN | | LAUNDRY ETC. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|