2002-01-02 00:00:00*************BUILDING UNSAT*************
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) INDICATE THE NUMBER OF COURSES OF
 BEAM BLOCK AND HORIZONTAL REINFORCEMENT
 THAT IS REQUIRED FOR THE FIRST AND
 SECOND FLOOR TIE BEAMS.
  
 3) THE DESIGN WIND LOADS FOR THE
 EXTERIOR DOORS OF THE STRUCTURE IS GIVEN
 ON SHEET 1 AS +/- 76 PSF. NONE OF THE
 PRODUCT APPROVALS FOR THE DOORS THAT
 WERE SUBMITTED HAVE DESIGN PRESSURES
 THAT HIGH. PLEASE REVIEW AND PROVIDE THE
 CORRECTED POSITIVE AND NEGATIVE DESIGN
 PRESSURES FOR ALL EXTERIOR DOOR OPENINGS
 OR THE WORST CASE IF YOU PREFER.
  
 4) PROVIDE PRODUCT APPROVALS FOR IMPACT
 RESISTANT ARCHED FIXED GLASS WINDOWS.
 THE TESTING INFORMATION SUBMITTED IS FOR
 A 4'X 8' RECTANGULAR FIXED WINDOW AND
 IS ONLY FOR THAT PARTICULAR WINDOW. IT
 ALSO MUST BE ACCOMPANIED BY A SITE
 SPECIFIC PRODUCT APPROVAL FORM SIGNED
 AND SEALED BY THE PRODUCT ENGINEER AND
 BY THE ENGINEER/ARCHITECT OF THE
 STRUCTURE, IF IT IS NOT A METRO-DADE OR
 SBCCI PRODUCT EVALUATION.
  
 5)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR STRUCTURAL MULLIONS.
  
 6) THE MEAN ROOF HEIGHT GIVEN ON SHEET 1
 OF THE CAST-CRETE DRAWINGS IS 24.25 FEET
 AND THE MEAN ROOF HEIGHT LISTED ON THE
 DESIGN COMPLIANCE FORM IS 28.7 FEET. THE
 STRUCTURE CAN ONLY HAVE ONE MEAN ROOF
 HEIGHT, THEREFORE THE TWO NUMBERS GIVEN
 SHOULD BE THE SAME. PLEASE CORRECT.
  
 7) THE OWNER/AGENT MUST SIGN AND DATE
 THE ENERGY FORMS IN THE SPACE PROVIDED
 ON THE FORM.
  
 8)PROVIDE A KEY PLAN AND AN INSTALLATION
 SCHEDULE FOR THE STORM PANELS,IN
 ADDITION TO THE PRODUCT APPROVALS WHICH
 WERE PROVIDED.
  
 9) PLEASE CLARIFY THE ATTACHMENT OF THE
 2X8 PT LEDGERS WITH 7&1/2" RED HEADS AT
 4'-0" O.C. AS INDICATED ON SHEET 6.
 THERE IS NO CONCRETE BEAM AT THIS
 ELEVATION AND THE FILLED VERTICLE CELLS
 ARE NOT ALL SPACED ON 4' CENTERS IN
 THIS AREA.
  
 10) THE WINDOW AND DOOR BUCK DETAILS AND
 THE FRAMING DETAILS FOR THE ARCHED
 OPENINGS ARE MISSING FROM THE NEW SETS
 OF DRAWINGS. PLEASE INCLUDE THEM WITH
 THE NEW PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202