2002-01-02 00:00:00 | *************BUILDING UNSAT************* |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) INDICATE THE NUMBER OF COURSES OF |
| BEAM BLOCK AND HORIZONTAL REINFORCEMENT |
| THAT IS REQUIRED FOR THE FIRST AND |
| SECOND FLOOR TIE BEAMS. |
| |
| 3) THE DESIGN WIND LOADS FOR THE |
| EXTERIOR DOORS OF THE STRUCTURE IS GIVEN |
| ON SHEET 1 AS +/- 76 PSF. NONE OF THE |
| PRODUCT APPROVALS FOR THE DOORS THAT |
| WERE SUBMITTED HAVE DESIGN PRESSURES |
| THAT HIGH. PLEASE REVIEW AND PROVIDE THE |
| CORRECTED POSITIVE AND NEGATIVE DESIGN |
| PRESSURES FOR ALL EXTERIOR DOOR OPENINGS |
| OR THE WORST CASE IF YOU PREFER. |
| |
| 4) PROVIDE PRODUCT APPROVALS FOR IMPACT |
| RESISTANT ARCHED FIXED GLASS WINDOWS. |
| THE TESTING INFORMATION SUBMITTED IS FOR |
| A 4'X 8' RECTANGULAR FIXED WINDOW AND |
| IS ONLY FOR THAT PARTICULAR WINDOW. IT |
| ALSO MUST BE ACCOMPANIED BY A SITE |
| SPECIFIC PRODUCT APPROVAL FORM SIGNED |
| AND SEALED BY THE PRODUCT ENGINEER AND |
| BY THE ENGINEER/ARCHITECT OF THE |
| STRUCTURE, IF IT IS NOT A METRO-DADE OR |
| SBCCI PRODUCT EVALUATION. |
| |
| 5)PROVIDE (2) CURRENT AND COMPLETE |
| COPIES OF SBCCI OR METRO-DADE PRODUCT |
| APPROVALS FOR STRUCTURAL MULLIONS. |
| |
| 6) THE MEAN ROOF HEIGHT GIVEN ON SHEET 1 |
| OF THE CAST-CRETE DRAWINGS IS 24.25 FEET |
| AND THE MEAN ROOF HEIGHT LISTED ON THE |
| DESIGN COMPLIANCE FORM IS 28.7 FEET. THE |
| STRUCTURE CAN ONLY HAVE ONE MEAN ROOF |
| HEIGHT, THEREFORE THE TWO NUMBERS GIVEN |
| SHOULD BE THE SAME. PLEASE CORRECT. |
| |
| 7) THE OWNER/AGENT MUST SIGN AND DATE |
| THE ENERGY FORMS IN THE SPACE PROVIDED |
| ON THE FORM. |
| |
| 8)PROVIDE A KEY PLAN AND AN INSTALLATION |
| SCHEDULE FOR THE STORM PANELS,IN |
| ADDITION TO THE PRODUCT APPROVALS WHICH |
| WERE PROVIDED. |
| |
| 9) PLEASE CLARIFY THE ATTACHMENT OF THE |
| 2X8 PT LEDGERS WITH 7&1/2" RED HEADS AT |
| 4'-0" O.C. AS INDICATED ON SHEET 6. |
| THERE IS NO CONCRETE BEAM AT THIS |
| ELEVATION AND THE FILLED VERTICLE CELLS |
| ARE NOT ALL SPACED ON 4' CENTERS IN |
| THIS AREA. |
| |
| 10) THE WINDOW AND DOOR BUCK DETAILS AND |
| THE FRAMING DETAILS FOR THE ARCHED |
| OPENINGS ARE MISSING FROM THE NEW SETS |
| OF DRAWINGS. PLEASE INCLUDE THEM WITH |
| THE NEW PLANS. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CALL: |