Plan Review Notes
Plan Review Notes For Permit 01091096
Permit Number 01091096
Review Stop E
Sequence Number 1
Notes
Date Text
2001-10-04 00:00:00************** UNSAT ****************
  
 PLEASE SEE REDLINED AREAS ON PLANS TO
 REFERENCE NEC REQ`MENTS.
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 3)NOTE: PLEASE NOTE THAT NO OTHER
 CIRCUITS ARE PERMITTED W/ KITCHEN OR
 BATHS. SEE 210-11-C-3/210-11-C-1.
  
 4)(NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50.
 PLEASE SHOW ON RISER DIAGRAM,
  
 5)NOTE: PLEASE NOTE THAT SERIVCE ENTRANC
 E CONDUCTORS/FEEDERS DO NOT MEET NEC.
 310-16/310-15
  
 6)NOTE:, PLEASE CLARIFY OCP FOR 5KW
 HEAT STRIP.
  
 7)NOTE: PLEASE NOTE MISSING OUTLETS
 PER 210-52
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
  
 ALSO, PLEASE NOTE THAT ALL PLANS THAT
 ARE SIGNED, DATED AND SEALED BY AN
 ENGINEER NEED TO HAVE TITLE ON ALL
 SHEETS. 61G15-23.002