Plan Review Notes For Permit 01091096 |
Permit Number |
01091096 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-10-04 00:00:00 | ************** UNSAT **************** | | | | PLEASE SEE REDLINED AREAS ON PLANS TO | | REFERENCE NEC REQ`MENTS. | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | 2) NOTE: PLEASE LIST THE REQ`D BATH(S) | | CIRCUIT(S) PER 210-11-C-3. | | MUST BE 20A AND #12AWG. | | | | 3)NOTE: PLEASE NOTE THAT NO OTHER | | CIRCUITS ARE PERMITTED W/ KITCHEN OR | | BATHS. SEE 210-11-C-3/210-11-C-1. | | | | 4)(NOTE: PLEASE SHOW GROUNDING ELECTRODE | | GOING TO BUILDING STEEL AND COLD WATER | | PER 250-50. | | PLEASE SHOW ON RISER DIAGRAM, | | | | 5)NOTE: PLEASE NOTE THAT SERIVCE ENTRANC | | E CONDUCTORS/FEEDERS DO NOT MEET NEC. | | 310-16/310-15 | | | | 6)NOTE:, PLEASE CLARIFY OCP FOR 5KW | | HEAT STRIP. | | | | 7)NOTE: PLEASE NOTE MISSING OUTLETS | | PER 210-52 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 | | | | | | ALSO, PLEASE NOTE THAT ALL PLANS THAT | | ARE SIGNED, DATED AND SEALED BY AN | | ENGINEER NEED TO HAVE TITLE ON ALL | | SHEETS. 61G15-23.002 |
|