Plan Review Notes For Permit 01091004 |
Permit Number |
01091004 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-09-24 00:00:00 | ***************** UNSAT **************** | | | | 1)NOTE: PLEASE NOTE THAT PLANS NEED TO | | BE SIGNED, DATED AND SEALED BY THE | | ENGINEER OF RECORD. PER FS/FAC 471.025 | | | | 2)NOTE: PLEASE NOTE THAT PLANS SHOW SD`S | | AS 120V INTERCONNECTED. PLANS ALSO SHOW | | LV FIRE ALARM SYSTEM. PLEASE CLARIFY. | | | | 3)NOTE: PLEASE CLARFIY NEW/ EMERGENCY | | LIGTHING? | | | | 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED, | | PLEASE NOTE THAT RATINGS WERE SUBMITTED | | FOR PANELS BUT NOT FOR MAIN/METER PANEL. | | PER 110-9. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|