Plan Review Notes For Permit 01090908 |
Permit Number |
01090908 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-12-08 00:00:00 | APPROVED WITH PROVISO: | | 1-FLOOD ZONE AO. NEED THE ELEVATION | | CERTIFICATE. | | 2-NEED ADDITIONAL SOIL BORINGS FOR EACH | | STRUCTURE AS RECOMMENDED ON THE PRE- | | LIMINARY SOIL TEST REPORT. | | 3-PROVIDE PRODUCT APPROVAL FOR FRENCH | | DOORS ASSEMBLIES AS SHOWN ON PLANS IF | | OPTION SELECTED. | | 4-PROVIDE MANUFACTURER'S CERTIFICATION | | FOR TWO HOUR FIRE RATED CONCRETE BLOCK | | ACCORDING TO THE BLOCK'S EQUIVALENT | | THICKNESS AND AGGREGATES USED. SEE | | SECTION 709.3 SBC 1997. | | 5-PROVIDE COMPLETE INFORMATION FOR STORM | | PANELS UNDER A SEPARATE PERMIT. | | 6-TRUSS DRAWINGS: | | -UPDATE ALL GENERAL TRUSS DETAILS. USE | | ASCE 7-95 FOR 140 MPH, NOT ASCE 7-93. | | SEE COMMENTS ON TRUSSES. | | | | | | NOTES: | | -DRAWINGS AND COMMENTS TO BE FILED UNDER | | PERMIT #01090908. | | -THESE COMMENTS APPLY TO PERMIT #S: | | 01090908, 01090911, 01090914, 01090918, | | 01090922 AND 01090924. |
|