2001-10-01 00:00:001) THE FIRE DEPARTMENT CONNECTION SHOWN
 ON SHEET FP3 FOR THIS THREE STORY
 BUILDING IS NOT CORRECT. THE FDC MUST
 BE FACED DIFFERENTLY AS THERE IS NO
 ACCESS TO THE LOCATION IT IS SHOWN.
 ALSO THIS DEVICE MUST BE WITHIN 150
 FEET OF A FIRE HYDRANT. PLEASE SUBMIT
 A REVISION.
 2) PLEASE BE ADVISED THAT THE STANDPIPE
 SYSTEM IN BUILDING THREE MUST PROVIDE
 750 GALLONS PER MINUTE AT THE ROOF
 AT 65 PSI.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910