2001-10-01 00:00:00 | 1) THE FIRE DEPARTMENT CONNECTION SHOWN | | ON SHEET FP3 FOR THIS THREE STORY | | BUILDING IS NOT CORRECT. THE FDC MUST | | BE FACED DIFFERENTLY AS THERE IS NO | | ACCESS TO THE LOCATION IT IS SHOWN. | | ALSO THIS DEVICE MUST BE WITHIN 150 | | FEET OF A FIRE HYDRANT. PLEASE SUBMIT | | A REVISION. | | 2) PLEASE BE ADVISED THAT THE STANDPIPE | | SYSTEM IN BUILDING THREE MUST PROVIDE | | 750 GALLONS PER MINUTE AT THE ROOF | | AT 65 PSI. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|