Plan Review Notes
Plan Review Notes For Permit 01090745
Permit Number 01090745
Review Stop FS
Sequence Number 1
Notes
Date Text
2001-09-24 00:00:001) NO FIRE DEPARTMENT CONNECTION SHOWN.
 2) CLUBHOUSE FIRE PROTECTION SHOWN.
 CLUBHOUSE FIRE SPRINKLER SYSTEM NOT
 PART OF THIS PERMIT AND SHOULD BE
 REMOVED FROM DRAWINGS.
 3) ONLY ONE FLOOR AND ROOF FIRE
 PROTECTION SHOWN. IF THE FLOOR PLAN IS
 THE SAME IT SHOULD BE NOTED AS TYPICAL
 ON THE DRAWINGS FOR ALL THREE FLOORS.
 4) PLANS ARE MISSING THE FOLLOWING
 A) POINT OF COMPASS
 B) CEILING CONSTRUCTION
 C) FULL HEIGHT CROSS SECTION
 D) LOCATION OF FIRE WALLS
 E) LOCATION OF PARTITIONS
 F) OCCUPANCY OF EACH ROOM OR AREA
 G) HANGER LOCATIONS
 H) NUMBER OF SPRINKLERS PER RISER, EACH
 FLOOR
 I) LOCATION OF ANY CONCEALED SPACES,
 ATTICS, CLOSETS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved