Date Text
2001-09-25 00:00:001) A NOTICE OF COMMENCEMENT IS REQUIRED
 PRIOR TO RECEIVING A PERMIT.
 2) CLUBHOUSE FIRE PROTECTION SHOWN.
 CLUBHOUSE FIRE SPRINKLER SYSTEM NOT
 PART OF THIS PERMIT AND SHOULD BE
 REMOVED FROM DRAWINGS.
 3) ONLY ONE FLOOR AND ROOF FIRE
 PROTECTION SHOWN. IF THE FLOOR PLAN IS
 TYPICAL ON THE DRAWINGS FOR ALL FLOORS
 IT SHOULD BE NOTED AS TYPICAL ON THE
 DRAWINGS.
 4) PLANS ARE MISSING THE FOLLOWING
 A) POINT OF COMPASS
 B) CEILING CONSTRUCTION
 C) FULL HEIGHT CROSS SECTION
 D) LOCATION OF FIRE WALLS
 E) LOCATION OF PARTITIONS
 F) OCCUPANCY OF EACH ROOM OR AREA
 G) HANGER LOCATIONS
 H) NUMBER OF SPRINKLERS PER RISER, EACH
 FLOOR
 I) LOCATION OF ANY CONCEALED SPACES,
 ATTICS, CLOSETS.
 PLEASE PROVIDE AN ENGINEER'S TITLE BLOCK
  