Plan Review Notes
Plan Review Notes For Permit 01090741
Permit Number 01090741
Review Stop FS
Sequence Number 1
Notes
Date Text
2001-09-25 00:00:001) A NOTICE OF COMMENCEMENT IS REQUIRED
 PRIOR TO RECEIVING A PERMIT.
 2) NO FIRE DEPARTMENT CONNECTION SHOWN.
 3) ONLY ONE FLOOR AND ROOF FIRE
 PROTECTION SHOWN. IF THE FLOOR PLAN IS
 THE SAME IT SHOULD BE NOTED AS TYPICAL
 ON THE DRAWINGS.
 4) PLANS ARE MISSING THE FOLLOWING
 A) POINT OF COMPASS
 B) CEILING CONSTRUCTION
 C) FULL HEIGHT CROSS SECTION
 D) LOCATION OF FIRE WALLS
 E) LOCATION OF PARTITIONS
 F) OCCUPANCY OF EACH ROOM OR AREA
 G) HANGAR LOCATIONS
 H) NUMBER OF SPRINKLERS PER RISER, EACH
 FLOOR
 I) LOCATION OF ANY CONCEALED SPACES,
 ATTICS, CLOSETS.
 PLEASE HAVE ENGINEER PROVIDE A TITLE
 BLOCK.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910