2002-01-03 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01090574
 2957 AUSTRALIAN AV
 CITY OF WEST PALM BEACH
 CONT ALMAZON BROTHERS
 TEL 793-1712
  
 SBC = 1997 STANDARD BUILDING CODE
  
 1)- THE DOCK PLANS DO NOT DEPICT THE
 REQUIRED GUARDRAIL AS REQUIRED SBC SEC-
 TION 1015. THE EXCEPTION FOR RESIDENTIAL
 BOAT DOCKS DOES NOT APPLY FOR PUBLIC USE
  
 2)- SBC 104.2.2 ADDITIONAL INFORMATION
 REQUIRED, THE PLANS DO NOT INDICATE WHAT
 % OF THE 16"X16" CEMENT LOUVERS ARE
 SOLID, NOT KNOWING THE PER CENTAGE OF
 OPEN AREA PER VENT ENABLES THE DETERMINA
 TION OF COMPLIANCE WITH THE 3 SQ FT OR
 GREATER REQUIREMENT FOR VENTILATION REQU
 IRED FOR RESTROOMS PER SBC 1203.4.2.
  
 3)- THE PRODUCT APPROVAL FOR THE STAND-
 ING SEAM METAL ROOF IS MISSING SBC 1503.
 3.2 (110 MPH). SBCCI OR DADE COUNTY
 REPORTS REQUIRED, 2 COPIES.
  
 FLORIDA STATE STATUTE 489.113 (B) WILL
 REQUIRE A ROOFING CONTRACTOR TO PULL
 THE ROOFING PERMIT.
  