2001-10-01 00:00:00************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT ON ELECTRICAL
 RISER DIAGRAM SHOWS CONDUITS W/ 6-#12`S
 GOING TO BATH BLDG AND STORAGE BLDGS./
 PLEASE NOTE THAT ON EP1.0, BATH BLDG
 SHOWS A 60AMP DISCONNECT? PLEASE CLARIFY
 HOW THIS IS BEING FED BY 6-#12`S?
  
 2)NOTE: PLEASE NOTE THAT BATH/AND
 STORAGE BLDGS ELECTRICAL NEEDS TO BE ON
 ELECTRICAL PLANS. PLEASE SHOW MEANS OF
 DISCONNECT FOR EACH. PER 225-31-32.
  
 3)NOTE: PLEASE NOTE THAT PLANS ARE TO BE
 SIGNED,DATED AND SEALED BY THE ENGINEER
 OF RECORD PER 471.025
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  