Plan Review Notes For Permit 01090574 |
Permit Number |
01090574 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-10-01 00:00:00 | ************** UNSAT ************** | | | | 1)NOTE: PLEASE NOTE THAT ON ELECTRICAL | | RISER DIAGRAM SHOWS CONDUITS W/ 6-#12`S | | GOING TO BATH BLDG AND STORAGE BLDGS./ | | PLEASE NOTE THAT ON EP1.0, BATH BLDG | | SHOWS A 60AMP DISCONNECT? PLEASE CLARIFY | | HOW THIS IS BEING FED BY 6-#12`S? | | | | 2)NOTE: PLEASE NOTE THAT BATH/AND | | STORAGE BLDGS ELECTRICAL NEEDS TO BE ON | | ELECTRICAL PLANS. PLEASE SHOW MEANS OF | | DISCONNECT FOR EACH. PER 225-31-32. | | | | 3)NOTE: PLEASE NOTE THAT PLANS ARE TO BE | | SIGNED,DATED AND SEALED BY THE ENGINEER | | OF RECORD PER 471.025 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|