Plan Review Notes For Permit 01090574 |
Permit Number |
01090574 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-10-10 00:00:00 | THE DOCK REQUIRES A GUARD RAIL IN | | ACCORDANCE WITH SBC 1015. | | | | ON SHEET C-3 OF 4 THE TWO ASSYMETRICAL | | PILINGS NEAR THE END OF THE DOCK DO NOT | | HAVE LOCATION DIMENSIONS. | | | | SHEET A3.0 PAGE 6 OF 8. SPECIFY THE | | SPACING OF THE #5 DOWEL/VERTICAL STEEL. | | | | ENSURE THAT THE TOILET ROOM LOUVERS | | PROVIDE THE 3 SQUARE FEET OR GREATER OF | | FREE AREA FOR VENTILATION REQUIRED BY | | SBC 1203.4.2. | | | | | | | | PLANS SUBMITTED FOR PUBLIC RECORD ARE | | REQUIRED TO HAVE THE EMBOSSED SEAL, | | DATE AND ORIGINAL SIGNATURE OF THE | | DESIGN PROFESSIONAL. |
|