Plan Review Notes
Plan Review Notes For Permit 01090574
Permit Number 01090574
Review Stop B
Sequence Number 1
Notes
Date Text
2001-10-10 00:00:00THE DOCK REQUIRES A GUARD RAIL IN
 ACCORDANCE WITH SBC 1015.
  
 ON SHEET C-3 OF 4 THE TWO ASSYMETRICAL
 PILINGS NEAR THE END OF THE DOCK DO NOT
 HAVE LOCATION DIMENSIONS.
  
 SHEET A3.0 PAGE 6 OF 8. SPECIFY THE
 SPACING OF THE #5 DOWEL/VERTICAL STEEL.
  
 ENSURE THAT THE TOILET ROOM LOUVERS
 PROVIDE THE 3 SQUARE FEET OR GREATER OF
 FREE AREA FOR VENTILATION REQUIRED BY
 SBC 1203.4.2.
  
  
  
 PLANS SUBMITTED FOR PUBLIC RECORD ARE
 REQUIRED TO HAVE THE EMBOSSED SEAL,
 DATE AND ORIGINAL SIGNATURE OF THE
 DESIGN PROFESSIONAL.