2001-10-06 00:00:00 | *************BUILDING UNSAT************* |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) THE 8050 HORIZONTAL SLIDING WINDOW |
| INTHE MASTER BEDROOM MUST COMPLY WITH |
| SEC.1005.4 OF THE 97 SBC FOR EMERGENCY |
| EGRESS REQUIREMENTS. (MINIMUM NET CLEAR |
| OPENING HEIGHT 24" AND WIDTH OF 20") |
| |
| 3) ONE OF THE INTERIOR BEARING WALLS |
| EXTENDS TO THE CENTER OF THE FRENCH |
| DOORS AT THE STUDY. INDICATE ON THE |
| PLANS THE SIZE OF THIS LOAD BEARING |
| HEADER. |
| |
| 4) THE ROOF SHEATHING AT GABLE ENDS IS |
| REQUIRED TO BE NAILED WITH 8D COMMON |
| NAILS AT 4"O.C. AT EDGES AND 6"O.C. |
| INTERMEDIATE WITHIN FIVE FEET (5') OF |
| THE ROOF EDGE INCLUDING OVERHANG. |
| |
| 5) THE ENERGY CODE INCORRECTLY LISTS |
| EXTERIOR WALLS AS WOOD FRAME WITH AN R |
| VALUE OF 4.2. PLEASE CORRECT. |
| |
| 6) TEMPORARY SALES OFFICE IN GARAGE OF |
| MODEL MUST BE APPROVED BY THE PLANNING |
| AND ZONING DEPARTMENT AND THE BUILDING |
| OFFICIAL. YOU WILL BE REQUIRED TO SUB- |
| MIT A PROPOSAL FOR REVIEW. THE FOLLOWING |
| ITEMS MUST BE ADDRESSED. ADDITIONAL |
| INFORMATION MAY BE REQUIRED AFTER REVIEW |
| BY BUILDING OFFICIAL. |
| A) A SURVEY SHOWING OFF STREET PARKING |
| ON A NON-DUSTING SURFACE. ONE SPACE FOR |
| EACH 350 SQ.FT. TO INCLUDE REQUIRED |
| ACCESSIBLE PARKING. |
| B) SALES OFFICE MUST MEET ACCESSIBILITY |
| REQUIREMENTS INCLUDING ACCESSIBLE TOILET |
| FACILITIES. |
| C)A CONDITIONAL CERTIFICATE OF OCCUPANCY |
| WILL BE REQUIRED BEFORE THE OFFICE CAN |
| BE OPENED. |
| THE FINAL C.O. FOR THE RESIDENCE WILL BE |
| ISSUED AFTER THE TEMPORARY COMPONENTS |
| HAVE BEEN REMOVED. |
| D) YOU MUST SUBMIT A LETTER FROM ONE OF |
| THE PRINCIPLES WITH THE COMPANY (SIGNED |
| AND SEALED OR WITH CORPRATE SEAL) TO THE |
| BUILDING OFFICIAL WITH YOUR REQUEST, |
| INDICATING THE LENGTH OF TIME THIS |
| CONDITION WILL EXIST AND THAT THE WALLS, |
| A/C DROPS, ETC. WILL BE REMOVED AND THAT |
| THE GARAGE DOOR WILL BE INSTALLED. |
| |
| 7) TEMPORARY EXTERIOR WALL MUST MEET |
| WINDLOAD REQUIREMENTS. PROVIDE A DETAIL |
| OF THIS WALL INDICATING ATTACHMENT TO |
| STRUCTURE. |
| |
| 8) PROVIDE PRODUCT APPROVALS FOR FRENCH |
| DOORS AND WINDOW. |
| |
| 9) PROVIDE IMPACT PROTECTION FOR FRENCH |
| DOORS AND WINDOW AT GARAGE. |
| |
| 10) PROVIDE DETAIL OF TRAP FENCE AT |
| GARAGE INDICATING TYPE OF CONSTRUCTION, |
| METHOD OF ANCHORING, ETC. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |