Date |
Text |
2001-10-25 00:00:00 | *************BUILDING UNSAT************* |
| |
| 1) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 2) PROVIDE (2) CURRENT AND COMPLETE |
| COPIES OF SBCCI OR METRO-DADE PRODUCT |
| APPROVALS FOR: |
| - SINGLE HUNG WINDOWS |
| - STRUCTURAL MULLIONS |
| - EXTERIOR DOOR |
| |
| 3) PROVIDE (2) PRODUCT APPROVALS, KEY |
| PLANS AND INSTALLATION SCHEDULES |
| INDICATING THE SPECIFIC TYPES OF ANCHORS |
| TO BE USED FOR STORM PANELS. MISSLE |
| IMPACT PROTECTION IS REQUIRED ON ALL |
| EXTERIOR GLAZED OPENINGS AT ENCLOSED |
| CARPORT. |
| |
| 4) INDICATE ON PLANS THAT BLOCKING WILL |
| BE PROVIDED AT WINDOW OPENINGS TO |
| PROVIDE ADEQUATE ATTACHMENT OF STORM |
| PANELS. |
| |
| 5)SHEET 4 OF THE PLANS HAS AN ENGINEER'S |
| TITLE BLOCK ON IT, THEREFORE, IT MUST |
| BE SIGNED, SEALED AND DATED BY THE |
| ENGINEER. |
| |
| 6) SHEET SHOWS 8" FROM FINISH GRADE TO |
| THE BOTTOM OF THE FOOTING. THE BOTTOM OF |
| THE FOOTIG MUST BE MINIMUM OF 12" BELOW |
| FINISH GRADE. 97 SBC SEC.1804.1.3 |
| PLEASE CORRECT. |
| |
| 7) THE BUILDING LINES FOR THE CARPORT |
| SHOWN ON THE SURVEY DOES NOT MATCH THE |
| PLANS. PLEASE CORRECT. NOTE: TWO (2) |
| COPIES OF SURVEY ARE REQUIRED. |
| |
| 8) PROVIDE ENERGY CALCULATIONS AND |
| EQUIPMENT SIZING CALCULATIONS (MANUAL J) |
| AS REQUIRED BY THE 1997 FLORIDA ENERGY |
| EFFICIENCY CODE FOR BUILDING |
| CONSTRUCTION. |
| |
| 9) PROVIDE A DRAWING SHOWING THE REAR |
| ELEVATION. |
| |
| 10) THE FOUNDATION PLAN INDICATES AN |
| EXISTING 8" BLOCK WALL. THE FLOOR PLAN, |
| ELEVATIONS AND WALL SECTION INDICATE |
| WOOD FRAME AND STUCCO. PLEASE CLARIFY. |
| |
| 11) INDICATE METHOD AND FASTENERS THAT |
| WILL BE USED TO ATTACH NEW WALLS TO |
| EXISTING CONCRETE COLUMNS AND STRUCTURE. |
| |
| 12) INDICATE ON PLANS HOW NEW FOOTINGS |
| WILL BE DOWELED INTO EXISTING FOOTINGS. |
| |
| 13) PROVIDE POSITIVE AND NEGATIVE |
| PRESSURES FOR EXTERIOR DOOR. PROVIDE |
| THE METHODS AND ASSUMPTIONS USED TO |
| DETERMINE THE 29# PRESSURES LISTED FOR |
| THE WINDOW OPENINGS THAT ARE GIVEN ON |
| THE PLANS AND USED TO DETERMINE |
| PRESSURES AT DOOR. |
| |
| 14) PROVIDE THE CALCULATIONS USED TO |
| DETERMINE THE TOTAL AND LIVE LOADS GIVEN |
| ON SHEET 4 (DESIGN LOAD ROOF). |
| |
| 15) PROVIDE THE DESIGN PARAMETERS AND |
| ASSUMPTIONS USED TO DETERMINE THE 25 PSF |
| UPLIFT GIVEN FOR THE ROOF ON SHEET 4. |
| |
| 16) PROVIDE THE SPECIES AND GRADE OF |
| THE EXISTING 2X8 RAFTERS ON 24" CENTERS. |
| THE RAFTERS ARE NOT CAPABLE OF SPANNING |
| 16' WITH THE ADDED WEIGHT OF A DRYWALL |
| CEILING. CHECK THE SPAN TABLES TO |
| DETERMINE WHERE ADDITIONAL RAFTERS MAY |
| BE REQUIRED. |
| |
| 17) THE STUCCO IS REQUIRED TO BE A TOTAL |
| OF 7/8" THICK MINIMUM ON THE EXTERIOR |
| WALLS PER 97 SBC SEC. 2504.2.1 AND |
| ASTM C926. PLEASE CORRECT. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |