Plan Review Notes For Permit 01090531 |
Permit Number |
01090531 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-10-09 00:00:00 | THE LEEDCO ENGINEERS ANALYSIS CITES THE | | 1994 STANDARD BUILDING CODE (SBC) AND A | | 135 MPH WIND SPEED.THE CITY IS | | CURRENTLY ENFORCING THE 1997 SBC. | | ALSO, THIS BUILDING IS A 100' +/- TALL, | | NOT THE 40' CALLED OUT.THE DESIGN | | INVESTIGATION SHOULD BE IN ACCORDANCE | | WITH | | ASCE 7-95 USING A WIND SPEED BETWEEN | | THE140 AND 150 MPH CONTOURS FOUND IN | | FIG. 6-1 OF THAT PUBLICATION. | | | | SHEET GN1, 1-1.11 RELATED DOCUMENTS, | | DOES NOT SHOW THE 1997 SBC AS THE | | BUILDING CODE DESIGN.THE BOCA CODE | | CITED ISNOT RECOGNIZED BY THE CITY NOR | | ARE SPECIFIC EDITIONS OF THE OTHER | | DESIGN STANDARDS NOTED. | | | | | | SHEET S3, PROVIDE AN ENGINEERING | | ANALYSIS OR TEST DATA FOR THE VARIOUS | | ANTENNAE'S ABILITYTO SUSTAIN THE | | WINDLOADS AT THIS LOCATION. |
|