Plan Review Notes
Plan Review Notes For Permit 01090531
Permit Number 01090531
Review Stop B
Sequence Number 1
Notes
Date Text
2001-10-09 00:00:00THE LEEDCO ENGINEERS ANALYSIS CITES THE
 1994 STANDARD BUILDING CODE (SBC) AND A
 135 MPH WIND SPEED.THE CITY IS
 CURRENTLY ENFORCING THE 1997 SBC.
 ALSO, THIS BUILDING IS A 100' +/- TALL,
 NOT THE 40' CALLED OUT.THE DESIGN
 INVESTIGATION SHOULD BE IN ACCORDANCE
 WITH
 ASCE 7-95 USING A WIND SPEED BETWEEN
 THE140 AND 150 MPH CONTOURS FOUND IN
 FIG. 6-1 OF THAT PUBLICATION.
  
 SHEET GN1, 1-1.11 RELATED DOCUMENTS,
 DOES NOT SHOW THE 1997 SBC AS THE
 BUILDING CODE DESIGN.THE BOCA CODE
 CITED ISNOT RECOGNIZED BY THE CITY NOR
 ARE SPECIFIC EDITIONS OF THE OTHER
 DESIGN STANDARDS NOTED.
  
  
 SHEET S3, PROVIDE AN ENGINEERING
 ANALYSIS OR TEST DATA FOR THE VARIOUS
 ANTENNAE'S ABILITYTO SUSTAIN THE
 WINDLOADS AT THIS LOCATION.